OPTIONaL SYSTEm TESTS
The following tests are available for verifying proper

operation of various functions of the gas detection

system:
– The Self Test and Response Test are accessed from

the “Display Test” screen. (A “Device Test” screen

is available for performing the same tests on HART

enabled detectors.)

– The Proof Test is performed by applying test gas

to the sensor. It is not accessed from the “Display

Test” screen and does not inhibit the outputs.

Main Menu
Process Vars
Display Status
Device Status
Display Setup
Device Setup
Device Cal
Display Test
Device Test

Display Test

Self Test
Response Test

Self-Test
This test commands the UD10-DCU to perform a fully

automatic internal test. At the completion of the test,

the UD10-DCU will indicate a pass or fail.

Response Test
This test inhibits the UD10-DCU’s outputs, thereby

providing a means of testing the system by applying

gas to the detector without activating any alarms or

affecting the output.

noTe

If the Response Test is not terminated by the
operator, the test will automatically time out after
ten minutes and the UD10-DCU will return to
normal operation.

Proof Test
A Proof Test (bump test) can be performed at any time

to verify proper operation and calibration of the system.

Since this test does not inhibit the UD10-DCU’s outputs,

secure any output devices prior to performing the test to

prevent unwanted actuation.

hISTORY
There are two separate histories, one for the display

and one for the detector (if available). Both will state

the number of hours that the unit has been operating,

and the highest and lowest recorded temperature (with

time and date stamp).

DISPLaY baCkLIghT OPERaTION
The UD10 can be programmed to turn on the backlight

feature of the digital display when an alarm or fault

occurs or a magnetic switch is activated. Navigate to

the Backlight Ctrl screen.

Main Menu

Process Vars

Display Status

Device Status

Display Setup

Device Setup

Device Cal

Display Test

Device Test

Display Setup

Mode Select
General Options
Input Loop Cal
Contrast Contrl
Backlight Ctrl

Backlight Ctrl

Off
On
Automatic

Off

= The backlight is always off.

On

= The backlight is always on.

automatic

= Normal operation – Backlight is off

Alarm – Backlight flashes on and off

Fault – Backlight is on steady

Magnetic Switch – Backlight is on steady

The backlight automatically turns off 10 minutes after the

last Magnetic Switch activation.

If the backlight is on following a magnetic switch

activation and then an alarm condition occurs, the

backlight will remain on steady and not flash until the 10

minute time-out is complete. Then it will begin flashing.