Calibration – Det-Tronics UD10 DCU Emulator FlexVu Universal Display Unit User Manual
Page 40
H-3
95-8656
4.2
cAlibrAtion
To initiate calibration of the PIRECL from the UD10-DCU
Display:
1. Using the magnet to activate the switches on the
UD10-DCU display, navigate to the “Calibration”
menu.
Main Menu
Process Vars
Display Status
Device Status
Display Setup
Device Setup
Device Cal
Display Test
Device Test
Device Cal
Cal Gas Conc
Cal Gas Type
Calibration
Cal Date
Calibration
Execute
Abort
2. Activate “Execute” (Enter/Select) to start calibration.
3. The UD10-DCU will display “Waiting for Zero” on
the main display screen, with a solid red LED on the
PIRECL housing illuminated.
4. The UD10-DCU will then display “Waiting for Gas”
on the screen, while the LED on the PIRECL is
flashing red.
5. Apply calibration gas to the PIRECL
6. The UD10-DCU will display “Waiting for Span” on
the screen, while a red flashing LED on the PIRECL
housing is illuminated.
7. When the UD10-DCU displays “Remove Cal Gas”
on the screen and the LED on the PIRECL housing
is off, remove the calibration gas.
8. After successful calibration, the UD10-DCU
automatically returns to the normal display with the
green LED illuminated on the PIRECL housing.
To initiate calibration from the PIRECL while monitoring
calibration using the UD10-DCU display:
1. Using the magnet, activate the magnetic calibration
switch on the PIRECL detector. See Figure below.
The LED turns from green to red.
2. The UD10-DCU will display “Waiting for Zero” on
the main display screen, with a solid red LED on the
PIRECL housing illuminated.
3. The UD10-DCU will then display “Waiting for Gas”
on the screen, while the LED on the PIRECL is
flashing red.
4. Apply calibration gas to the PIRECL detector.
5. The UD10-DCU will display “Waiting for Span” on
the screen, while a red flashing LED on the PIRECL
housing is illuminated.
6. When the UD10-DCU displays “Remove Cal Gas”
on the screen and the LED on the PIRECL housing
is off, remove the calibration gas.
7. After successful calibration, the UD10-DCU
automatically returns to the normal mode with the
green LED illuminated on the PIRECL
CALIBRATION MAGNET
CALIBRATION NOZZLE
MULTICOLOR LED
HART COMMUNICATION PORT
(COVER INSTALLED)
PLACE CALIBRATION MAGNET
HERE TO ACTIVATE INTERNAL
REED SWITCH
B2435
Model PIRECL Gas Detector