Det-Tronics UD10 DCU Emulator FlexVu Universal Display Unit User Manual

Page 5

background image

3

95-8656

4.2

Quick access/Shortcut: Fault menu
To access the fault menu quickly, when a fault is present,

touch the magnet to the glass by the PREVIOUS

button.

DEvICE ENCLOSURE
The UD10-DCU housing is a 5 port aluminum or stainless

steel explosion-proof junction box with a clear viewing

window.

DEvICE DISPLaY
The UD10-DCU is provided with a 160 x 100 dot matrix

backlit LCD display. See Figure 1.

During normal operation, the LCD continuously

displays the detected gas level, gas type, and units

of measurement. The real time clock can also be

displayed if desired.

The display shows the following alarm information:
• High gas alarm
• Low gas alarm
• Aux alarm

The display indicates the following fault information:
• Device fault
• Display fault

The UD10-DCU has smart capabilities to allow easy

access to the following information:
• Detector information
• Measurement range
• Alarm setpoints
• Alarm and event logs

For detailed menu structure, refer to the appropriate

Appendix.

CONFIgURaTION OvERvIEw
The user must select the sensor mode/type manually

from the UD10-DCU display. The selection options

are:

HART Device (including Generic HART Device)
PIR9400
C706x
505
NTMOS
CGS
Generic Device (without HART)

When “HART Device” is selected, the UD10-DCU

communicates with the detector to determine the device

type. The upper and lower range for the UD10-DCU

display is determined by the detector type and must be

selected before configuration data is sent from the EQP

system. If the detector type or range is changed at the

UD10-DCU, a configuration download from S3 should

again be performed.

Alarm levels and calibration gas concentration level

come from the S3 application. Configuration information

is downloaded from S3 to the controller, which sends

the data to the LON interface board in the UD10-DCU.

The LON interface then sends configuration information

to the main processor in the UD10-DCU for storage and

display. Alarm levels and calibration gas concentration

cannot be set from the UD10-DCU menu system,

however, they can be viewed after download.

Status information from the UD10-DCU and attached

detector is passed to the EQP controller over the LON

network, and then to S3 for display.