Calibration, Menu structure – Det-Tronics UD10 DCU Emulator FlexVu Universal Display Unit User Manual

Page 56

background image

4.2

95-8656

K-4

cAlibrAtion

To initiate calibration of the C706x sensor from the

UD10-DCU Display:

1. Using the magnet to activate the switches on the

UD10-DCU display, navigate to the “Calibrate”

menu.

2. Activate “Execute” (Enter/Select) to start calibration.

3. The UD10-DCU will display “Waiting for Zero” on the

main display screen as it performs zero calibration.

4. When zero calibration is complete, the UD10-DCU

will display “Waiting for Gas” on the screen.

5. Apply calibration gas to the sensor.

6. The UD10-DCU will display “Waiting for Span”

on the screen while the span calibration is being

performed.

7. When the UD10-DCU displays “Remove Cal Gas”

on the screen, remove the calibration gas from the

sensor.

8. When calibration is complete, “Remove Cal Gas”

is no longer displayed on the screen and the

UD10-DCU automatically returns to the normal

operating mode.

menu structure

UD10-DCU with C706x Series Sensor
Refer to the following menu when using the UD10-DCU’s

LCD display and internal magnetic switches.

menu HeLp

Status menus only allow the user to view the data.
The Setup menus allow the user to both view and
edit the data.

Main Menu
Process Vars
Display Status
Device Status
Display Setup
Device Setup
Device Cal
Display Test

Device Cal

Calibration
Cal Gas Conc

Calibration

Execute
Abort