95-8656

4.2

D-1

AppenDix D

IECEx aPPROvaL DESCRIPTION

Ex d IIC T5 Gb

Tamb –40°C to +75°C

IECEx FMG 08.0010x

IP66

Performance verified in accordance with:

IEC 60079-29-1.

Special Conditions for Safe Use (‘X’):

The UD10-DCU control unit complies with IEC 60079-29-1 when connected to a Detector Head with an IEC

certificate of conformity to IEC 60079-29-1.

noTe

Consideration must be given to overall Gas System Performance Requirements.

WarnIng

When a sensor/detector is connected directly to the UD10 housing, the lower ratings of the two devices

will prevail.