beautypg.com

Appendix g, Wiring – Det-Tronics UD10 DCU Emulator FlexVu Universal Display Unit User Manual

Page 34

background image

G-1

95-8656

4.2

AppenDix G

UD10-DCU with PIR9400 POINTwaTCh IR gaS DETECTOR

noTe

For complete information regarding the PIR9400 Gas Detector, refer to instruction manual 95-8440.

WirinG

4000

3500

3000

2500

2000

1500

1000

500

0

18

19

20

21

22

23

24

25

26

27

28

29

30

Power Supply Voltage

Dist

ance in f

t.

UD10-DCU with PIR9400

12
14
16
18

AWG

Wire Size

Notes: Maximum cable length from power source to UD10 is 2000 feet.

Maximum cable length from UD10 to PIR9400/PIRTB termination box is 2000 feet.

PIR9400

POINTWATCH

BLACK

RED

YELLOW

WHITE

GREEN

SEE NOTE 1

NOTE 1

CONNECT THE GREEN SENSOR LEAD

TO THE CHASSIS GROUND LUG ON THE

INSIDE BOTTOM OF THE DISPLAY ENCLOSURE.

NOTE 2

UD10 HOUSING MUST BE ELECTRICALLY

CONNECTED TO EARTH GROUND.

A2513

Sensor Connector

Power Supply Connector

LON Connect

or

J4

J3

J7

24 VDC

24 VDC

+

SHIELD

24 VDC

24 VDC

+

SHIELD

SHIELD

C

ALIBR

A

TE

24 VDC

4-20 mA

24 VDC

+

J4-1

J4-2

J4-3

J4-4

J4-5

J7

-6

J7

-5

J7

-4

J7

-3

J7

-2

J7

-1

SHIELD

2 B COM

2 A COM

SHIELD

1 B COM

1 A COM

J3-1

J3-2

J3-3

J3-4

J3-5

J3-6

UD10

DISPLAY UNIT

SW3

J2

ON

PIR9400 Wired Directly to UD10-DCU