Det-Tronics UD10 DCU Emulator FlexVu Universal Display Unit User Manual
Page 19
17
95-8656
4.2
Device Faults
Description
Recommended action
EE Fault
Fault in non-volatile memory
Power may have been interrupted while the device
was updating its internal data logs. Recycle
power.
Ref ADC Sat
Sensor signal level is outside the range of the AD
converter
Return to factory.
Active ADC Sat
Sensor signal level is outside the range of the AD
converter
Return to factory.
24V Fault
Problem in 24 volt power supply or power wiring
Check power wiring and output voltage of power
supply.
Flash CRC Fault
Memory fault
Return to factory.
RAM Fault
Fault in volatile memory
Return to factory.
Low Voltage
Power supply voltage outside of limits
Check power supply voltage.
Return to factory.
Temp Fault
Temperature sensor fault
Return to factory.
Software Fault
Internal software fault
Return to factory.
EE Safety Fault
Internal configuration fault
Return to factory.
Gas Under Range
Sensor signal has drifted negative
Device may have been calibrated with background
gas present. Recalibrate the detector. Purge with
clean air if needed.
Sensor Mismatch
Wrong sensor type is installed
Sensor type must match configuration. Change
sensor or configuration.
ADC CNTR Fault
Internal hardware fault
Return to factory.
3V Fault
3 volt internal power supply out of tolerance
Return to factory.
Comm Fault
Communication fault
Check detector wiring and power supply.
GEN Fault
Unspecified fault
Verify correct power wiring and supply voltage.
Consult the factory.
12V Fault
12 volt internal power supply out of tolerance
Return to factory.
5V Fault
5 volt internal power supply out of tolerance
Return to factory.
Table 6—Troubleshooting Guide - Device Faults, Continued