UD10-DCU with gENERIC 4-20 ma SENSORS

noTe

For complete information regarding installation, wiring, and calibration of the sensor, refer to the instruction
manual provided by the sensor manufacturer.

operAtion

The UD10-DCU can be used with generic sensors

that generate a calibrated linear 4-20 mA signal, with

or without HART. The UD10-DCU allows the operator

to select the upper and lower range values and unit

of measurement. The UD10-DCU then analyzes the

4-20 mA input signal from the sensor and displays the

value with the designated measurement unit, and also

controls the alarm outputs.

UPPER aND LOwER RaNgE vaLUES
The upper range value (URV) and lower range value

(LRV) are selected using the magnetic tool and the

UD10-DCU’s menu system (Main Menu > Device

Setup). The URV corresponds to the 20 mA signal while

the LRV corresponds to 4 mA. The default values are

0 for the LRV and 100 for the URV. When the generic

detector supports HART communication, the URV and

LRV come from the attached detector.

mEaSUREmENT UNIT TExT
The operator can select the appropriate measurement

unit from a pre-entered list: % (default), PPM, LFL, or

PPB, or he can enter his own custom 4-character string.

Measurement unit text is displayed on the main screen

with the process variable. When the generic detector

supports HART communication, the unit text comes

from the attached detector.

LOw FaULT ThREShOLD
The operator can enter a low input fault threshold in the

range of 0.5 to 4 mA (default is 3.5 mA). When the input

signal is at or below this point, an “Out of Range Low

Fault” is annunciated. This feature can be enabled/

disabled as desired.

hIgh FaULT ThREShOLD
The operator can enter a high input fault threshold in the

range of 20 to 27 mA (default is 21 mA). When the input

signal is at or above this point, an “Out of Range High

Fault” is annunciated. This feature can be enabled/

disabled as desired.

aLaRmS
The Low, High and Auxiliary alarm levels are

independently field adjustable. Alarm levels are set

and displayed with the selected measurement units. All

alarm levels must be within the LRV to URV range.

aLaRm LaTChINg
Latching or non-latching function is independently

selectable for each alarm. The default setting is

non-latching. Latched alarms can be reset with a “Reset

Latched Alarms” command from the menu system or a

power cycle.

SENSOR CaLIbRaTION
The UD10-DCU does not support generic sensor

calibration. Generic sensors must be pre-calibrated

following the procedure described in the instruction

manual provided by the sensor manufacturer.

4-20 ma OUTPUT REaDINg
While in Generic mode, the UD10-DCU displays values

below the 4 mA level to allow the use of 0-20 mA

sensors.

menu structure

UD10-DCU with generic 4-20 ma Sensors
Refer to the following menus when using the

UD10-DCU’s LCD display and internal magnetic

switches. Two different menus are provided to

accommodate sensors with or without HART

communication.

menu HeLp

Status menus only allow the user to view the data.
The Setup menus allow the user to both view and
edit the data.