instAllAtion

wIRINg REQUIREmENTS
The simplest installation involves installing the sensor

into one of the UD10-DCU openings and connecting

the wiring directly to the UD10-DCU. If the installation

requires separation of the C706x sensor and the

UD10-DCU Display, the sensor can be connected to

a STB sensor termination box, and the C706x/STB

combination wired to the UD10-DCU. In this case,

shielded cable is recommended to help protect against

interference caused be extraneous electrical “noise.” In

applications where the cable is installed in conduit, the

conduit should not be used for wiring to other electrical

equipment whenever possible. If other equipment

power wiring is run in the same conduit, the cabling

must

be shielded. The maximum allowable distance

between the C706x sensor and UD10-DCU Display

Unit is limited by the resistance of the cabling used.

INSTaLLaTION aND wIRINg PROCEDURE
1. Determine the best mounting locations for the

detectors.

2. Install the C706x sensor within the proper opening

in the UD10-DCU or STB junction box. Mount the

UD10-DCU/C706x with the sensor oriented vertically

and the opening pointing down. The UD10-DCU

should be electrically connected to earth ground.

noTe

The electrochemical sensor cell does not need
to be installed within the C706X housing while
installing and wiring the detector/junction box.
It is recommended to keep the sensor in the
manufacturer’s sealed shipping bag in a cool
storage environment until actual power-up and
calibration commissioning is performed. This
will ensure that the sensor will provide maximum
longevity.

3. Terminate all three C706x conductors at the proper

terminals. Refer to the appropriate illustration for

details.

4. Double check that all wiring is the proper size

and type and has been installed correctly. Check

operating voltage at the C706x sensor and the

UD10-DCU Display Unit.

noTe

Do not apply power to the system with the junction
box cover removed unless the area has been de-
classified.

5. Proceed with startup and calibration.