Configuring the sfp temperature threshold – Allied Telesis AT-S65 User Manual
Page 35

AT-S65 Management Software User’s Guide
35
4. From the Line Card Temperature Configuration Menu, select Module
Number.
5. Type the number of the line card where the SFP is located and press
Enter.
6. Select Maximum Temperature Threshold.
7. Enter a number for the Maximum Temperature Threshold and press
Enter.
The highest possible maximum temperature is 120° C. The default is
75°C.
8. After you have adjusted the parameters, return to the Main Menu.
Configuring the
SFP Temperature
Threshold
To set the temperature threshold for an SFP in a line card, perform the
following procedure:
1. From the Main Menu, select System Configuration.
The System Configuration Menu is shown in Figure 4 on page 22.
2. From the System Configuration Menu, select Temperature Threshold
Configuration and press Enter.
The Temperature Threshold Configuration Menu is shown in Figure 9
on page 33.
3. From the Temperature Threshold Configuration Menu, select SFP
Temperature Threshold Configuration and press Enter.
The SFP Temperature Threshold Configuration Menu is shown in
Figure 12.
Figure 12. SFP Temperature Threshold Configuration Menu
4. From the SFP Temperature Threshold Menu, select Module Number.
5. Type the number of the line card where the SFP is installed.
6. Select Maximum Temperature Threshold.
SFP Temperature Threshold Menu
Module Number:1
Maximum Temperature Threshold: 70
Return to Temperature Threshold Configuration Menu ...