SmartStix I/O Module Produced (Transmitted) Global Data
Table 6.12 – Produced Global Data Word 1
16-bit Word
8-bit High Byte
8-bit Low Byte
Digital Input Status Data - Low Word
I16
I15
I14
I13
I12
I11
I10
I9
I8
I7
I6
I5
I4
I3
I2
I1
I16…I1
Monitors the Off / On state of the SmartStix I/O Module’s 1st 16 Digital Inputs, if any.
Table 6.13 – Produced Global Data Word 2
16-bit Word
8-bit High Byte
8-bit Low Byte
Digital Input Status Data - High Word
I32
I31
I30
I29
I28
I27
I26
I25
I24
I23
I22
I21
I20
I19
I18
I17
I32…I17
Monitors the Off / On state of the SmartStix I/O Module’s 2nd 16 Digital Inputs, if any.
Table 6.14 – Produced Global Data Word 3
16-bit Word
8-bit High Byte
8-bit Low Byte
Module Fault Data
Network Fault Data
Configuration Status Data
PUP
I/O
ROM
RAM
LIFE
ID
DUP
NAK
SIT
SHT
SLT
SLT
CLT command status; matches CLT when command is complete
SHT
CHT command status; matches CHT when command is complete
SIT
CIT command status; matches CIT when command is complete
NAK
Network Acknowledge test failed; found no other Network devices
DUP
Network Duplicate ID test failed; found another Network device with our Network ID
ID
Network ID test failed; Network ID rotary switches illegally set to 00, FE or FF
LIFE
Network Life Expectancy Time has expired; outputs are in default state
RAM
Module RAM test failed; found a RAM memory fault during power-up-self-test
ROM
Module ROM test failed; found a ROM memory fault during power-up-self-test
I/O
Module I/O test failed; found an I/O fault during power-up-self-test
PUP
Module just powered up; using default configuration; outputs are Off
Table 6.15 – Produced Global Data Word 4
16-bit Word
8-bit High Byte
8-bit Low Byte
Firmware Revision Status Data
Device Identification Status Data
0.00 to 2.55 = Version Number
0 to 255 = Device Class Number
Device Class Number
SmartStix I/O Module’s numeric product identifier (see
Table 6. 3
).
Version Number
SmartStix I/O Module’s numeric firmware identifier
6.10
Produced Global Data Power-Up Initialization
At power-up, a SmartStix I/O Module’s four Produced Global Data words are initialized as follows:
1. Digital Inputs are read and loaded into Words 1 and 2.
2. Power-up-self-test result is loaded into Word 3; if tests passed, only PUP bit is On.
3. Module’s Device Class Number and Version Number are loaded into Word 4.
4. All four Produced Global Data words are transmitted to the CsCAN Network.