Num Words – This is the number of words to receive from the remote I/O device. Up to four words can
be received from the remote I/O device. The function of these words are described in Table 6.1.

Table 6.1 -

Consumed / Produced Parameter Descriptions

Consumed Directed
Digital Data Words

Function

Affects

Word 1 (bits 1 to 16)

Controls on/off state of digital outputs 1-16.

Relay or Digital output SmartStix

Word 2 (bits 17 to 32)

Controls on/off state of digital outputs 17-32.

Relay or Digital output SmartStix

Word 3 (bits 33 to 48)

Specifies whether SmartStix uses default
configuration or values from Word 4.

Relay and Digital input and output

Word 4 (bits 49 to 64)

Sets digital inputs / heartbeat and life
expectancy time data.

Relay and Digital input and output

Word 5 (bits 65 to 80)

Sets the default state of outputs 1-16.

Relay and Digital output

Word 6 (bits 81 to 96)

Sets the default state of outputs 17-32.

Relay and Digital output

Word 7 (bits 97 to 112)

Determines if default state is on or off for
outputs 1-16.

Relay and Digital output

Word 8 (bits 113 to 128)

Determines if default state is on or off for
outputs 17-32.

Relay and Digital output

Produced Global
Digital Data Words

Function

Affects

Word 1 (bits 1 to 16)

On/off state of inputs 1-16.

Digital input SmartStix

Word 2 (bits 17 to 32)

On/off state of inputs 17-32.

Digital input SmartStix

Word 3 (bits 33 to 48)

Status bits and diagnostic data

Relay or Digital input and output

Word 4 (bits 49 to 64)

Device class number and firmware identifier
sent by SmartStix module.

Relay or Digital input and output


Note: Table 6.1 summarizes SmartStix I/O module consumed and produced data words. For advanced

users, refer to pages 58 and 60 for sections describing the Consumed and Produced words in
detail.


6.4.3

Put Remote I/O Function Block


This function handles sending data to a remote I/O device block obtained from a set of registers specified
by the user. This function passes power flow if the remote I/O device is behavi ng normally. This function
does not pass power flow if the remote I/O device has not sent a heartbeat in 2000 milliseconds. This
function sends heartbeat messages to the output device every 1000 milliseconds. The default remote I/O
operation is to expect heartbeat messages at least every 2000 milliseconds; otherwise the outputs are
turned off (or their configured default state). Data is normally transmitted on change of state or if the
remote I/O device is power-cycled.

A remote I/O device consists of a CsCAN device such as SmartStix Modules that transmit global data and
receive directed network data.