beautypg.com

Horner APG RCS SmartStix User Manual

Page 58

background image

PAGE 58

15 MAR 2003

CH.6

MAN0305-02


6.7

SmartStix I/O Module Consumed (Received) Directed Data

Table 6.4 – Consumed Directed Data Word 1

16-bit Word

8-bit High Byte

8-bit Low Byte

Digital Output Control Data – Low Word

Q16

Q15

Q14

Q13

Q12

Q11

Q10

Q9

Q8

Q7

Q6

Q5

Q4

Q3

Q2

Q1


Q16…Q1 Controls the Off / On state of the SmartStix I/O Module’s 1st 16 Digital Outputs, if any.

Table 6.5 – Consumed Directed Data Word 2

16-bit Word

8-bit High Byte

8-bit Low Byte

Digital Output Control Data - High Word

Q32

Q31

Q30

Q29

Q28

Q27

Q26

Q25

Q24

Q23

Q22

Q21

Q20

Q19

Q18

Q17


Q32…Q17 Controls the Off / On state of the SmartStix I/O Module’s 2nd 16 Digital Outputs, if any.

Table 6.6 – Consumed Directed Data Word 3

16-bit Word

8-bit High Byte

8-bit Low Byte

Diagnostic Command Data

Configuration Command Data

Reserved for Future Products

CIT

CH

T

CL

T

CLT = 0

Command the SmartStix I/O Module to set its Life Expectancy Time to 2.0 seconds, as the maximum
time to wait between Control Station to SmartStix I/O Module output control data messages, before
setting all Digital Outputs to their default states.


CLT = 1

Command the SmartStix I/O Module to use Word 4’s Life Expectancy Time. In this case, a value of 0.0
disables the Life Expectancy feature.


CHT = 0

Command the SmartStix I/O Module to set its Heartbeat Send Time to 1.0 second, as the minimum time
between SmartStix I/O Module to Control Station Heartbeat messages.


CHT = 1

Command the SmartStix I/O Module to use Word 4’s Heartbeat Send Time. In this case, a value of 0.0
disables the Heartbeat Send feature.


CIT = 0

Command the SmartStix I/O Module to send its Digital Input data to the Control Station, only when the
Digital Inputs change state.


CIT = 1

Command the SmartStix I/O Module to use Word 4’s Digital Input Send Time, to determine how often to
periodically send its Digital Input data to the Control Station. In this case, a value of 0.0 disables
automatic sending of Digital Input data.


Note:

Regardless of the CIT setting, Digital Inputs are always sent to the Control Station when the
SmartStix I/O Module powers -up, and when specifically requested by the Control Station.

Table 6.7 – Consumed Directed Data Word 4

16-bit Word

8-bit High Byte

8-bit Low Byte

Digital Input / Heartbeat Send Time Data

Life Expectancy Time Data

0.0 to 25.5 seconds = Minimum Send Interval

0.0 to 25.5 seconds = Maximum Receive Interval


See Directed Data Word 3’s CLT, CHT and CIT command descriptions above.

This manual is related to the following products: