3.7
System Menu Option Screens
In addition to providing access to the MiniOCS / MiniRCS, configuration parameters, the System Menu
also provides power-up and runtime status. For brevity, both configuration and status fields are covered
in this section
There are up to ten different menu options, which include the following:
•
Set Network ID
•
Set Network Baud
•
Set Contrast
•
View OCS(RCS) Status
•
View OCS(RCS) Diags
•
View I/O LEDs
•
View OCS(RCS) Model
•
Set Fkeys Mode
•
Set RS232 Mode.
•
Set Time/Date
•
Set Network ID
This screen contains two fields. The first field contains the current network status. The second field
contains the current Network ID of the model. The second field is numerically editable and is used to
configure the Network ID.
Each unit on the network needs a unique ID number. The correct ID number should be entered here
before physically attaching the unit to the network.
Cscan model:
[ 1 - 253 ]
DeviceNet model:
[ 0 - 63 ]
Note: If the Network ID setting is changed, the unit stops executing the ladder code (for up to 1 second)
while the network is re-tested. If the “Network OK?” status changes from “Yes” to “No,” the new Network
ID is a duplicate, and another ID needs to be selected.
•
Set Network Baud
This screen contains an editable enumerated field allowing the user to select the current baud rate of the
network.
Cscan model:
[125K, 250K, 500K, 1M]
DeviceNet model:
[125K, 250K, 500K]
Note: All devices on the network must be at the same baud rate. A device configured for the wrong
baud rate may shut down the network entirely.
•
Set Contrast
This menu contains an editable bar graph entry allowing the user to set the contrast of the LCD display.