CH.6

15 MAR 2003

PAGE 59

MAN0305-04

Table 6.8 – Consumed Directed Data Word 5

16-bit Word

8-bit High Byte

8-bit Low Byte

0 = Force Off / On 1 = Hold-Last-State Default Digital Output Data - Low Word

H16

H15

H14

H13

H12

H11

H10

H9

H8

H7

H6

H5

H4

H3

H2

H1


H16…H1

Determines default state of the SmartStix I/O Module’s 1st 16 Digital Outputs, if any, when
the configured Life Expectancy Time expires. If an H bit is 1, its corresponding Digital
Output, by default, holds its last state. If an H bit is 0, its corresponding Digital Output is
forced Off or On, depending on the corresponding F bit in Word 7 (

Table 6.10

).

Table 6.9 – Consumed Directed Data Word 6

16-bit Word

8-bit High Byte

8-bit Low Byte

0 = Force Off / On 1 = Hold-Last-State Default Digital Output Data - High Word

H32

H31

H30

H29

H28

H27

H26

H25

H24

H23

H22

H21

H20

H19

H18

H17


H32…H17 Determines default state of the SmartStix I/O Module’s 2nd 16 Digital Outputs, if any, when

the configured Life Expectancy Time expires. If an H bit is 1, its corresponding Digital
Output, by default, holds its last state. If an H bit is 0, its corresponding Digital Output is
forced Off or On, depending on the corresponding F bit in Word 8 (

Table 6.11

).

Table 6.10 – Consumed Directed Data Word 7

16-bit Word

8-bit High Byte

8-bit Low Byte

0 = Force Off 1 = Force On Default Digital Output Data - Low Word

F16

F15

F14

F13

F12

F11

F10

F9

F8

F7

F6

F5

F4

F3

F2

F1


F16…F1

Determines default Off or On state of each of the SmartStix I/O Module’s 1st 16 Digital
Outputs, if any, when the configured Life Expectancy Time expires, and when the
corresponding H bit in Word 5 (

Table 6.8

) is 0.

Table 6.11 – Consumed Directed Data Word 8

16-bit Word

8-bit High Byte

8-bit Low Byte

0 = Force Off 1 = Force On Default Digital Output Data - High Word

F32

F31

F30

F29

F28

F27

F26

F25

F24

F23

F22

F21

F20

F19

F18

F17


F32…F17 Determines default Off or On state of each of the SmartStix I/O Module’s 2nd 16 Digital

Outputs, if any, when the configured Life Expectancy Time expires, and when the
corresponding H bit in Word 6 (

Table 6.9

) is 0.


6.8

Consumed Directed Data Power-Up Initialization


At power-up, the SmartStix I/O Module’s eight Consumed Directed Data words are all cleared to 0. Until
Directed Data is actually received from a Control Station, the SmartStix I/O Module will exhibit the
following behavior:

1. All Digital Outputs are Off, until Q data is received from a Control Station.
2. The device expects to receive Q data at least every two seconds.
3. The device transmits a Heartbeat every second.
4. The device transmits its Digital Input data, only when the Digital Inputs change state.
5. If Q data is received, and then not received for 2 seconds, the outputs go Off again.
6. At power-up, a request for Directed Data is transmitted to the CsCAN Network.