Horner APG RCS SmartStix User Manual
Page 42
PAGE 42
15 MAR 2003
CH.3
MAN0305-04
DeviceNet In - (DeviceNet model only.)
Ok
DeviceNet master is maintaining a polled connection and not sending IDLE.
Warn The DeviceNet master is no longer maintaining a polled connection or sending IDLE.
(IDLE is a network state in which ‘some’ masters maintain a polled connection but sends
zero data if an associated PLC controller is in IDLE mode. Refer to Master
documentation for more information.)
Clock Error - This test checks that the real time clock contains valid data.
Ok
The real time clock contains valid data.
Warn Indicates invalid data in the real time clock.
I/O System - This test checks that the configured (downloaded) model number matches the physical
I/O module installed in the controller.
Ok
The configured model number matches the installed I/O module.
Warn Indicates the configured model number does not match the installed I/O module.
(See View OCS(RCS) Model system screen for more information.)
•
View I/O LEDs
The View I/O LEDs simulate the LEDs and show the statuses of the first 16 %I and first 16 %Q registers.
•
View OCS(RCS) Model
The View OCS(RCS) Model screen allows the user to view the MiniOCS / MiniRCS model number.
When viewing the model number, the following status screens are possible. Note the term OCSxxx (or
RCSxxx) refers to the MiniOCS (or MiniRCS) model number such as OCS082 (or RCS082).
a.
If the Mini model number is not configured and no I/O module is installed, the message
" I/O: Empty” is displayed.
b.
If the Mini model number is not configured but has an I/O module installed, the message
"+Mini OCSxxx (or RCSxx)" is displayed.
c.
If the Mini model number is configured but no I/O module is installed, the message
"-I/O Missing" is displayed.
d.
If the configured Mini model number does not match the installed I/O module, the message
"?Mini OCSxxx (or RCSxx)" is displayed.
e.
If the installed I/O module is not supported by the Mini firmware, the message
“*Unsupported” is displayed. The module is either defective or an Engine firmware upgrade is
required to support the module.
f.
If the installed I/O module has erroneous or outdated firmware in it, the message
“fMini OCSxxx (or RCSxx)" is displayed. The module is either defective or a Module firmware
upgrade is required.
g.
If the installed I/O module has a configuration error, the message
"cMini OCSxxx (or RCSxx)" is displayed. The configuration data for that module is incorrect.
h.
If the configured Mini model number matches the installed I/O module, the message
" Mini OCSxxx (or RCSxx)" is displayed.