beautypg.com

Red Lion MDC User Manual

Page 37

background image

DEDICATED FUNCTION AND USER INPUTS

Refer to the Terminal Connections drawing. TBA is the bottom terminal

block and TBB is the top terminal block.

RUN (TBB8): A momentary closure to common on the

RUN input causes the MDC to accelerate the motor from

STOP mode to the current speed setpoint using the

current ramp rate.

- R-STOP (TBB-9) and F-STOP (TBB-10) must be held

low or tied to common (TBB-3).

- MDC must be in the Indication Display or User Setpoints Module.

- MDC may not be in JOG mode.

R-STOP (TBB9): A momentary open from common on the

R-STOP input causes the MDC to decelerate the motor

from its current speed to STOP mode using the current

ramp rate.

- MDC must be in RUN mode. R-STOP is inoperative in

JOG mode.

F-STOP (TBB10): A momentary open from common on the

F-STOP input causes the MDC to execute a fast stop,

taking the analog Drive Output signal immediately to zero

volts. The motor deceleration is limited only by the motor

drive system. This is an emergency stop function. The

drive Enable Output goes immediately to its inactive state and may be used

to engage braking or remove power from the motor via an external relay.

- F-STOP overrides all other active function inputs for as long as the

F-STOP input remains active. The function priority from highest to

lowest is: F-Stop, Jog, R-Stop, and Run. To lock out all other input

functions, use a maintained switch on the F-Stop input.

F-STOP is operative in RUN and JOG modes and the Program

Diagnostics Menu.

Note: This does not guarantee that the drive is disabled unless the Drive

Enable Output is used with an external relay to disconnect AC drive power.

JOG (TBB11): The jog function is only available from the

STOP mode. A sustained closure from the JOG input to

common causes the MDC to accelerate the motor to the

jog speed setpoint using the jog ramp rate. The motor will

remain at the jog speed until the closure is removed, at

which point the MDC will execute an F-STOP.

- Operative from STOP mode only.

- R-STOP (TBB-9) and F-STOP (TBB-10) must be held low or tied to

common (TBB-3).

- MDC must be in the Indication Display or User Setpoint Module.

OPEN LOOP (TBB12): A maintained closure to common on

this input causes the MDC to run open loop. The error

correction value, Trim, is set to zero and speed is not

regulated. A momentary closure on this input can be used as a

Trim reset, to momentarily reset the Trim value to zero.

USER INPUTS 1 to 4 (TBB4 to 7): The User Input terminals require a

closure to common to execute a programmable function. The action

required may be maintained or momentary depending upon the function.

The functions available are: View Display, Change Display, Reset Alarm,

Setpoint Select, Ramp Select, Ramp Override, Increment Setpoint,

Decrement Setpoint, and Program Disable. For a complete description of

these functions, see the Program User Menu.

ALARM OUTPUTS 1 AND 2

The alarm outputs are open collector solid state outputs. They are

programmable for High Alarm, Low Alarm, Deviation Alarm and Zero

Speed Alarm functions. For details, see the Program Alarms Menu and the

Block Diagram.

DRIVE ENABLE OUTPUT

The Drive Enable Output (TBA #7) provides an open collector closure to

common whenever the MDC is in a RUN or JOG mode. It is inactive (open)

only when the MDC is in STOP mode. This output may be used to control a

relay which removes power from the motor and drive in STOP mode (see

Block Diagram for details).

-35-