beautypg.com

Red Lion MDC User Manual

Page 24

background image

PROGRAM ALARMS MENU

Alarm parameters 1 and 2 activate solid state Alarm Outputs 1

and 2 respectively. A manual reset, which requires the use of a

User Input, will reset an Alarm Output (see Program User Menu).

Both alarms may be programmed for any of the five alarm

functions: High Alarm, Low Alarm, Deviation Alarm, Zero

Speed Alarm, and Disabled. The following flowchart shows only

the Alarms portion:

ALARM TYPES

High Alarm (HIGH ALM)

The alarm output activates when the feedback input registers a

speed greater than or equal to the alarm value in display units.
Low Alarm (LOW ALM)

The alarm output activates when the feedback input registers

a speed less than or equal to the alarm value in display units. The

alarm may be active or inactive in stop mode (see Stop Enabled

or Disabled).
Deviation Alarm (DEV ALM)

The alarm output activates when the feedback input registers a

speed outside of a ± band around the current speed or ratio

setpoint. The band is equal to the ± alarm value in display speed

units. The alarm may be active or inactive in stop mode (see Stop

Enabled or Disabled).

For Example: A speed setpoint of 1000, with an alarm setpoint

of 10 would activate the alarm when the speed fell below 990 or

went above 1010.
Zero Speed Alarm (ZERO SPD)

The alarm output activates when the feedback input receives no

input pulse for at least 1 second. There is no alarm value

associated with the Zero Speed Alarm.

Disabled

The alarm output is inactive when disabled.

-22-