beautypg.com

Red Lion GEMINI 42 User Manual

Page 49

background image

-47-

11. SERIAL COMMUNICATIONS:

Type - Bi-directional 20 mA current loop, 20 mA source provided. (Powers up

to 7 units in a loop with internal current source.)

Baud Rate - Programmable 300 to 2400.

Maximum Address - 16 units. (Actual number in a single loop is limited by

serial hardware specifications.)

Data Format - 10 bit frame, Odd parity (one start bit, 7 data bits, one odd

parity bit, and one stop bit.)

Serial Hardware Specifications -

SO - Output Transistor Rating: V

max

= 30 VDC, V

SAT

= 1 V

max

at 20 mA

SI - Input Diode Rating: V

F

= 1.25 V

TYP

; 1.5 V

max

Note: The compliance voltage rating of the source must be greater than the

sum of the voltage drops around the loop.

12. OUTPUT(S):

Solid-State - Current sinking NPN open collector transistors. I

SNK

= 100 mA

max. @ V

CE

= 1 V. V

OH

= 30 VDC max. (Internal Zener diode protection).

Relays - Mounted on a field replaceable PC board. Form C contacts rated at 5

amps @ 120/240 VAC or 28 VDC (resistive load), 1/8 H.P. @ 120 VAC

(inductive load). The operate time is 5 msec nominal and the release time is 3

msec nominal.

Relay Life Expectancy - 100,000 cycles at Max. Rating. (As load level

decreases, life expectancy increases.)

Programmable Timed Outputs - The timed outputs can be set from 0.01 to

599.99 seconds, ±(0.01% + 10 msec.).

13. CERTIFICATIONS AND COMPLIANCES:

SAFETY

IEC 61010-1, EN 61010-1: Safety requirements for electrical equipment

for measurement, control, and laboratory use, Part 1.

IP65 Enclosure rating (Face only), IEC 529

Type 4 Enclosure rating (Face only), UL50

ELECTROMAGNETIC COMPATIBILITY:

Immunity to EN 50082-2

Electrostatic discharge

EN 61000-4-2 Level 2; 4 Kv contact

1

Level 3; 8 Kv air

Electromagnetic RF fields

EN 61000-4-3 Level 3; 10 V/m

80 MHz - 1 GHz

Fast transients (burst)

EN 61000-4-4 Level 4; 2 Kv I/O

Level 3; 2 Kv power

2

RF conducted interference

EN 61000-4-6 Level 3; 10 V/rms

150 KHz - 80 MHz

Power frequency magnetic fields EN 61000-4-8 Level 4; 30 A/m

Emissions to EN 50081-2

RF interference

EN 55011

Enclosure class A

Power mains class A

Notes:

1. Metal bezel of unit connected with ground from rear bezel screw to

metal mounting panel.

2. When the unit is DC powered, a power line filter (RLC#LFIL0000 or

equivalent) was installed, so as not to impair the function of the unit.

Refer to the EMC Compliance Installation section of the manual for

additional information.

14. ENVIRONMENTAL CONDITIONS:

Operating Temperature: 0 to 50°C

Storage Temperature: -40 to 70°C

Operating and Storage Humidity:

85% max. RH (non-condensing) from 0°C to 50°C.

Altitude: Up to 2000 meters

15. CONSTRUCTION:

Metal die-cast bezel, plastic case. This unit is rated for NEMA 4/IP65 indoor

use. Installation Category II, Pollution Degree 2

16. WEIGHT: 2.1 lbs. (0.9 Kg)

DUAL COUNTER MODE [41 2]

MODE

X1

X2

X4

Uni or Bi-directional

9 KHz

4.5 KHz

Anti-Coincidence Add/Subtract

5 KHz

2.5 KHz

Separate Input

7.5 KHz

3.5 KHz

Quadrature

4.5 KHz

4 KHz

2.5 KHz

This manual is related to the following products: