Easicool™ precision air conditioning, Technical data upflow units wx type, Operating limits – Airedale EasiCool 6kW 64kW User Manual
Page 91

EasiCool™
Precision Air Conditioning
Technical Data Upflow Units WX Type
Performance Data
91
EasiCool Technical Manual 7535776 V1.1.0_04_2013
Te
ch
nic
al
W
X - T
yp
e
380
V
6
0H
z
V
380
V
6
0H
z
Cooling Capacity (1)
Condenser Entering/Leaving Temperature - Based on 5°C ΔT
Air On
25°C/30°C
30°C/35°C
35°C/40°C
40°C/45°C
(DB°C/%RH) TC (kW) SC (kW)
THR
(kW)
TC (kW) SC (kW)
THR
(kW)
TC (kW) SC (kW)
THR
(kW)
TC (kW) SC (kW)
THR
(kW)
V40WX-EZRE-1
22/50
40.6
40.6
54.4
40.6
40.6
54.4
39.9
39.9
54.1
38.0
38.0
53.2
24/45
42.2
42.2
56.1
42.2
42.2
56.1
41.5
41.5
55.8
39.6
39.6
55.0
26/40
43.8
43.8
57.8
43.8
43.8
57.8
43.2
43.2
57.5
41.4
41.4
56.9
V40WX2-EZRE-1
22/50
42.2
42.2
56.3
42.2
42.2
56.3
41.6
41.6
56.0
39.7
39.7
55.5
24/45
43.8
43.8
57.9
43.8
43.8
57.9
43.1
43.1
57.7
41.3
41.3
57.3
26/40
45.4
45.4
59.7
45.4
45.4
59.7
44.8
44.8
59.5
43.0
43.0
59.1
V45WX2-EZRE-1
22/50
48.4
46.8
64.2
48.4
46.8
64.2
47.7
46.4
64.0
45.6
45.0
63.2
24/45
50.0
50.0
66.0
50.0
50.0
66.0
49.3
49.3
65.7
47.3
47.3
65.0
26/40
51.7
51.7
67.8
51.7
51.7
67.8
51.0
51.0
67.5
49.0
49.0
66.9
V50WX2-EZRE-1
22/50
51.7
50.8
69.5
51.7
50.8
69.5
50.8
50.2
69.1
48.3
48.3
68.2
24/45
53.6
53.6
71.6
53.6
53.6
71.6
52.7
52.7
71.2
50.2
50.2
70.2
26/40
55.5
55.5
73.6
55.5
55.5
73.6
54.6
54.6
73.2
52.1
52.1
72.2
V55WX2-EZRE-1
22/50
59.5
55.5
80.6
59.5
55.5
80.6
58.5
54.9
80.2
55.8
53.3
79.1
24/45
61.6
59.7
82.8
61.6
59.7
82.8
60.5
59.1
82.3
57.8
57.3
81.2
26/40
63.5
63.5
84.9
63.5
63.5
84.9
62.4
62.4
84.4
59.7
59.7
83.2
V60WX2-EZRE-1
22/50
67.5
62.1
91.2
67.5
62.1
91.2
66.2
61.3
90.6
63.0
59.4
89.2
24/45
69.7
66.6
93.6
69.7
66.6
93.6
68.4
65.8
93.0
65.1
63.8
91.6
26/40
71.8
71.4
95.9
71.8
71.4
95.9
70.5
70.5
95.3
67.2
67.2
93.9
TC = Total Cooling
SC = Sensible Cooling
THR = Total Heat Rejection
(1) All data quoted is gross
(2) Interpolate for water temperatures between those quoted, do not extrapolate
(3) Water flow rate (l/s) = THR/(4.19*ΔT) at 100% Water; for glycol use refer to Ethylene Glycol Correction Factors section
Indoor Air Temperature
+18°C to +28°C
Indoor RH%
+40% to +55%
Condenser Minimum Entering Temperature °C
+25°C
Condenser Maximum Leaving Water Temperature °C
+45°C
Operating Limits