Electrical data -2, Easicool™ precision air conditioning, Technical data – Airedale EasiCool 6kW 64kW User Manual
Page 189: Te ch nic al o utd oo r

EasiCool™
Precision Air Conditioning
Technical Data
Electrical Data -2
CR12
CR16
CR22
CR30
Unit Data
(1)
Nominal Run Amps
A
1.72
1.72
3.02
3.02
Maximum Start Amps
A
6.02
6.02
7.7
7.7
Recommended Mains Fuse
A
6
6
6
6
Max Mains Cable Incoming
mm²
6
6
6
6
Mains Supply
220V / 2Ph / 60Hz
Fan - Per Fan
Quantity
1
1
1
1
Motor Size
kW
0.39
0.39
0.64
0.64
Full Load Amps
A
1.72
1.72
3.02
3.02
Locked Rotor Amps
A
6.02
6.02
7.7
7.7
OPTIONAL EXTRAS
Short Case Axial Fan - Per Fan
Quantity
1
1
1
1
Motor Size
kW
0.82
0.82
1.75
1.75
Full Load Amps
A
3.5
3.5
7.8
7.8
Locked Rotor Amps
A
8.75
8.75
19.5
19.5
EC Condenser Fan - Per Fan
Quantity
1
1
1
1
Motor Size
kW
0.75
0.75
0.73
0.73
Full Load Amps
A
3.4
3.4
3.3
3.3
(1)
Nominal data based on 35°C ambient and a 50°C mean condensing temperature and using standard fan.
189
EasiCool Technical Manual 7535776 V1.1.0_04_2013
Te
ch
nic
al
O
utd
oo
r