Technical data, Performance data, Easicool™ precision air conditioning – Airedale EasiCool 6kW 64kW User Manual
Page 183: Te ch nic al, Outd oo r, Operating limit

EasiCool™
Precision Air Conditioning
Mean Condensing
Ambient
Temperature °C
25°C
30°C
35°C
40°C
45°C
48°C
Output kW Output kW Output kW Output kW Output kW Output kW
CR12
35
8.8
3.3
-
-
-
-
40
13.8
8.8
3.4
-
-
-
45
19
14
8.9
3.6
-
-
50
24.4
19.2
14.1
9.1
3.8
-
55
29.8
24.7
19.5
14.4
9.3
4.1
CR16
35
11.9
5
-
-
-
-
40
18.2
12
5.2
-
-
-
45
24.7
18.4
12.1
5.4
-
-
50
31.3
25
18.6
12.3
5.6
-
55
38.2
31.8
25.4
19
12.6
6.5
CR22
35
15.4
6.2
-
-
-
-
40
24
15.5
6.4
-
-
-
45
32.8
24.2
15.7
6.7
-
-
50
41.7
33.1
24.6
16
7
-
55
51
42.3
33.7
25.1
16.4
7.7
CR30
35
19.8
8.1
-
-
-
-
40
30.6
20
8.4
-
-
-
45
41.7
30.9
20.2
8.7
-
-
50
53.1
42.1
31.3
20.5
9.2
-
55
64.8
53.8
42.8
31.9
21
9.8
Technical Data
Performance Data
(1)
Output kW refers to the condenser heat rejection.
Standard Variable Speed Head Pressure Control
Minimum Ambient Air DB °C
-20°C
Maximum Ambient Air DB °C
+48
Optional On/Off Head Pressure Control
Minimum Ambient Air DB °C
-0°C
Maximum Ambient Air DB °C
+48
Operating Limit
(1)
For conditions outside those quoted, please contact Airedale.
(2)
Low ambient kits are available for applications with temperatures below those quoted, please contact Airedale.
Te
ch
nic
al
183
EasiCool Technical Manual 7535776 V1.1.0_04_2013
O
utd
oo
r