Easicool™ precision air conditioning, Technical data, Te ch ni ca l o utd oo r – Airedale EasiCool 6kW 64kW User Manual
Page 188: Electrical data -1

EasiCool™
Precision Air Conditioning
CR50
CR65
CR80
CR105
Unit Data
(1)
Nominal Run Amps
A
5.8
5.8
8.7
8.7
Maximum Start Amps
A
11.2
11.2
16.8
16.8
Recommended Mains Fuse
A
10
10
16
16
Max Mains Cable Incoming
mm²
6
6
6
6
Mains Supply
230V / 1Ph + N / 60Hz
Fan - Per Fan
Quantity
2
2
3
3
Motor Size
kW
0.63
0.63
0.63
0.63
Full Load Amps
A
2.9
2.9
2.9
2.9
Locked Rotor Amps
A
5.6
5.6
5.6
5.6
OPTIONAL EXTRAS
Short Case Axial Fan - Per Fan
Quantity
2
2
3
3
Motor Size
kW
1.4
1.4
1.4
1.4
Full Load Amps
A
6
6
6
6
Locked Rotor Amps
A
18
18
18
18
EC Condenser Fan - Per Fan
Quantity
2
2
3
3
Motor Size
kW
0.77
0.77
0.77
0.77
Full Load Amps
A
3.3
3.3
3.3
3.3
Technical Data
Electrical Data -1
(1)
Nominal data based on 35°C ambient and a 50°C mean condensing temperature and using standard fan.
188
EasiCool Technical Manual 7535776 V1.1.0_04_2013
Te
ch
ni
ca
l
O
utd
oo