Easicool™ precision air conditioning, Technical data downflow units x type, Electrical data v13x - v17x – Airedale EasiCool 6kW 64kW User Manual
Page 131

EasiCool™
Precision Air Conditioning
131
EasiCool Technical Manual 7535776 V1.1.0_04_2013
Te
ch
nic
al
X-T
yp
e
22
0V
6
0H
z
V
V13X-EZRE-2
V15X-EZRE-2
V17X-EZRE-2
Standard Condenser Match - X
CR22
CR22
CR30
Unit Data Full Function - X
(1)
Nominal Run Amps
A
47.4
49.0
52.6
Maximum Start Amps
A
151.8
153.7
190.7
Recommended Mains Fuse Size
A
63
63
63
Unit Data Cooling Only - X
(2)
Nominal Run Amps
A
27.7
29.3
33.0
Maximum Start Amps
A
132.1
134.0
171.0
Recommended Mains Fuse Size
A
32
40
40
Max Mains Incoming Cable Size
mm²
35
35
35
Mains Supply
V
220V / 3PH / 60HZ
Control Circuit
VAC
24
24
24
Evaporator Fan - Motor Per Fan
Centrifugal Forward Curved DD EC - Designed to 25Pa ESP
Maximum Electrical Input Power
(3)
kW
2.2
1.9
1.9
Full Load Amps
A
9.1
8
8
Locked Rotor Amps
A
22.8
20
20
Compressor - Per Compressor
Quantity x Motor Size
kW
1 x 5,53
1 x 6.57
1 x 7.82
Nominal Run Amps
A
15.6
18.3
21.9
Locked Rotor Amps
A
120
123
160
Type Of Start
Direct On Line
Standard Condenser Match - AC Motor - Per Fan
Electrical Input Power
kW
0.64
0.64
0.64
Full Load Amps
A
3.02
3.02
3.02
OPTIONAL EXTRAS
Electric Heating
Stage Of Reheat
1
1
1
Number Of Elements
3
3
3
Rating
kW
7.5
7.5
7.5
Current Per Phase
A
19.68
19.68
19.68
Humidifier
Capacity
kg/hr
3
3
3
Rating
kW
2.25
2.25
2.25
Full Load Amps
A
5.90
5.90
5.90
Evaporator Fan Options
Larger Fan Motor - AC Motor - Per Fan
Centrifugal Forward Curved AC - Designed to 25Pa ESP
Electrical Input Power
(3)
kW
N/A
N/A
N/A
Full Load Amps
A
N/A
N/A
N/A
Locked Rotor Amps
A
N/A
N/A
N/A
Standard Size Motor - EC Motor - Per Fan
Centrifugal Backward Curved DD EC - Designed to 25Pa ESP
Electrical Input Power
(3)
kW
1.01
1.01
1.01
Full Load Amps
A
3.2
3.2
3.2
Condenser Fan Options
Standard Condenser Motor - EC Motor - Per Fan
Electrical Input Power
kW
0.73
0.73
0.73
Full Load Amps
A
3.3
3.3
3.3
Technical Data Downflow Units X Type
Electrical Data
V13X - V17X
Mechanical
(1)
Entering air 24°C/45% RH ambient 35°C.
(2)
Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.
(3)
With Standard forward curved fan motors; Machine weight includes a refrigerant charge.
(4)
Backward curved EC fan options quote electrical power. All other options quote shaft power.
(5)
For refrigerant charges, refer to
Unit Refrigerant Charge (kg/Circuit)
.
(6)
Based on air temperature of 15.5°C leaving the evaporator coil.
(7)
Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to
Low Pressure Hot Water
.
Electrical
(1)
Values given for full function units (incl. electric heating, humidification and matched condenser) at 7°C evaporating and 54.4°C condensing with standard
forward curved fan motors, for optional data, please contact Airedale.
(2)
Values given for Cooling only units (incl. Compressor, evaporator fan and matched condenser) at 7°C evaporating and 54.4°C condensing, for optional
data, please contact Airedale.
(3)
Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.