Electrical data -1, Easicool™ precision air conditioning, Technical data – Airedale EasiCool 6kW 64kW User Manual
Page 187: Te ch nic al o utd oo r

EasiCool™
Precision Air Conditioning
CR12
CR16
CR22
CR30
Unit Data
(1)
Nominal Run Amps
A
1.1
1.1
2.9
2.9
Maximum Start Amps
A
2.8
2.8
5.6
5.6
Recommended Mains Fuse
A
6
6
6
6
Max Mains Cable Incoming
mm²
6
6
6
6
Mains Supply
230V / 1Ph + N / 60Hz
Fan - Per Fan
Quantity
1
1
1
1
Motor Size
kW
0.24
0.24
0.63
0.63
Full Load Amps
A
1.1
1.1
2.9
2.9
Locked Rotor Amps
A
2.8
2.8
5.6
5.6
OPTIONAL EXTRAS
Short Case Axial Fan - Per Fan
Quantity
1
1
1
1
Motor Size
kW
0.61
0.61
1.4
1.4
Full Load Amps
A
2.8
2.8
6
6
Locked Rotor Amps
A
7
7
18
18
EC Condenser Fan - Per Fan
Quantity
1
1
1
1
Motor Size
kW
0.7
0.7
0.77
0.77
Full Load Amps
A
3.1
3.1
3.3
3.3
Technical Data
Electrical Data -1
(1)
Nominal data based on 35°C ambient and a 50°C mean condensing temperature and using standard fan.
187
EasiCool Technical Manual 7535776 V1.1.0_04_2013