Easicool™ precision air conditioning, Technical data, Te ch ni ca l o utd oo r – Airedale EasiCool 6kW 64kW User Manual
Page 184: Performance data, Operating limit

EasiCool™
Precision Air Conditioning
Mean Condensing
Ambient
Temperature °C
25°C
30°C
35°C
40°C
45°C
48°C
Output kW Output kW Output kW Output kW Output kW Output kW
CR50
35
33.7
13.7
-
-
-
-
40
52.6
34
14.2
-
-
-
45
71.7
53.1
34.4
14.8
-
-
50
91.3
72.5
53.8
35.1
15.5
-
55
111.5
92.6
73.7
54.8
35.9
16.9
CR65
35
44.9
18.6
-
-
-
-
40
69.1
45.2
19.3
-
-
-
45
93.8
69.7
45.6
20
-
-
50
119.2
94.8
70.6
46.4
21
-
55
145.5
120.9
96.4
72
47.5
22.6
CR80
35
55.3
23
-
-
-
-
40
85.8
55.8
23.8
-
-
-
45
116.7
86.6
56.5
24.7
-
-
50
148.4
118.1
87.8
57.5
25.8
-
55
180.9
150.4
120
89.5
58.9
28.3
CR105
35
72.1
30
-
-
-
-
40
110.8
72.6
31
-
-
-
45
150.4
111.7
73.3
32.2
-
-
50
191.1
152.1
113.2
74.5
33.8
-
55
233.3
193.8
154.6
115.5
76.3
36.4
Technical Data
Performance Data
(1)
Output kW refers to the condenser heat rejection.
Standard Variable Speed Head Pressure Control
Minimum Ambient Air DB °C
-20°C
Maximum Ambient Air DB °C
+48
Optional On/Off Head Pressure Control
Minimum Ambient Air DB °C
-0°C
Maximum Ambient Air DB °C
+48
Operating Limit
(1)
For conditions outside those quoted, please contact Airedale.
(2)
Low ambient kits are available for applications with temperatures below those quoted, please contact Airedale.
184
EasiCool Technical Manual 7535776 V1.1.0_04_2013
Te
ch
ni
ca
l
O
utd
oo
r