Refrigerant Pipesizing Guide - X Type Downflow
Pipe lengths calculated for Indoor unit with Airedale Outdoor Unit match.
(1)
For interconnecting pipework with a predominantly horizontal layout.
(2)
For interconnecting pipework with a predominantly vertical layout.
IMPORTANT
Tandem Compressor and suction throttle valve applications: In part load, gas velocity should be taken into account
when selecting and commissioning pipework to ensure full oil return.
IMPORTANT
REMEMBER excessive pressure loss in interconnecting pipework will impair system performance; this should be
factored in during the design of the system and where necessary oil separators employed.
Indoor
Outdoor
Indoor Unit
Equivalent Pipe Lengths with R410A
Connection Size
0-15m
15-40m
Liquid
Discharge
Liquid
Discharge
Liquid
Discharge
Horizontal(1)
Vertical(2)
Horizontal(1)
Vertical(2)
DF8X
CR16
3/8”
1/2”
3/8”
1/2”
1/2”
3/8”
5/8”
1/2”
DF10X
CR16
3/8”
1/2”
3/8”
5/8”
1/2”
3/8”
5/8”
1/2”
DF13X
CR22
3/8”
5/8”
3/8”
5/8”
1/2”
1/2”
3/4”
5/8”
DF15X
CR22
3/8”
5/8”
1/2”
5/8”
5/8”
1/2”
3/4”
5/8”
DF17X
CR30
3/8”
5/8”
1/2”
3/4”
5/8”
1/2”
7/8”
5/8”
DF20X2
CR30
1/2”
7/8”
1/2”
3/4”
5/8”
1/2”
7/8”
3/4”
DF22X2
CR50
1/2”
7/8”
1/2”
3/4”
5/8”
5/8”
7/8”
3/4”
DF26X2
CR50
1/2”
7/8”
1/2”
3/4”
3/4”
5/8”
7/8”
7/8”
DF28X
CR50
1/2”
7/8”
5/8”
7/8”
3/4”
5/8”
7/8”
7/8”
DF31X
CR50
1/2”
7/8”
5/8”
7/8”
7/8”
5/8”
1 1/8”
7/8”
DF35X
CR50
1/2”
7/8”
5/8”
7/8”
7/8”
5/8”
1 1/8”
7/8”
DF40X
CR65
5/8”
1 1/8”
5/8”
1 1/8”
7/8”
3/4”
1 1/8”
7/8”
DF45X
CR80
5/8”
1 1/8”
5/8”
1 1/8”
1 1/8”
3/4”
1 1/8”
1 1/8”
DF50X2
CR80
5/8”
1 3/8”
3/4”
1 1/8”
1 1/8”
3/4”
1 1/8”
1 1/8”
DF55X2
CR80
5/8”
1 3/8”
3/4”
1 1/8”
1 1/8”
3/4”
1 1/8”
1 1/8”
DF60X2
CR80
5/8”
1 3/8”
3/4”
1 1/8”
1 1/8”
7/8”
1 1/8”
1 1/8”