Easicool™ precision air conditioning, Dimensional & installation data, Ins ta lla tio n – Airedale EasiCool 6kW 64kW User Manual
Page 34: Dimensions

EasiCool™
Precision Air Conditioning
(1)
Standard forward airflow direction.
(2)
Optional reverse airflow direction.
(3)
Optional gland plate and panel for side services access via the right side of unit. For services details contact Airedale.
(4)
Base mains cable entry.
(5)
Standard base gland plate entry for refrigeration/water services. For services details contact Airedale.
(6)
Shaded area denotes fan discharge aperture. Optional EC fan motor discharge aperture provided with protective mesh, not shown.
(7)
M6 fixing hole positions.
67
0
A
64
0
27
0
15
20
0
B
15
200
30
A
B
A
7
B
B
30
9
10
8
19
40
670
6 - 10
990
13 - 17
1310
20 - 26
1
2
3
67
0
A
64
0
27
0
15
20
0
B
15
200
D
C
F
G
A
B
D
C
A
5
B
B
D
C
D
E
4
6
7
19
40
670
6 - 10
990
13 - 17
1310
20 - 26
1
2
6
67
0
A
64
0
27
0
15
20
0
B
15
200
D
C
F
G
A
B
D
C
A
5
B
B
D
C
D
E
4
5
3
4
Dimensional & Installation Data
Dimensions
V8 - V26 - Standard Airflow Configuration (mm) with Standard EC Fan Motors
19
40
670
6 - 10
990
13 - 17
1310
20 - 26
1
2
3
67
0
A
64
0
27
0
15
20
0
B
15
200
D
C
F
G
A
B
D
C
A
7
B
B
D
C
D
E
8
8
6
7
9
10
H x D x W
A
B
C
D
E
F
G
V8
X/WX
mm
1940 x 670 x 670
640
270
183
304
N/A
50
268
V10
X/WX
mm
1940 x 670 x 670
640
270
167
337
N/A
50
295
V13
X/WX
mm
1940 x 670 x 990
960
590
387
337
N/A
50
295
V15
X/WX
mm
1940 x 670 x 990
960
590
355
401
N/A
50
347
V17
X/WX
mm
1940 x 670 x 990
960
590
355
401
N/A
50
347
V20
X2/WX2
mm
1940 x 670 x 1310
1280
455
166
337
303
50
295
V22
X2/WX2
mm
1940 x 670 x 1310
1280
455
166
337
303
50
295
V26
X2/WX2
mm
1940 x 670 x 1310
1280
455
166
337
303
50
295
34
EasiCool Technical Manual 7535776 V1.1.0_04_2013
Ins
ta
lla
tio
n