Technical data upflow units x type - 2, Performance data, Easicool™ precision air conditioning – Airedale EasiCool 6kW 64kW User Manual
Page 122

EasiCool™
Precision Air Conditioning
122
EasiCool Technical Manual 7535776 V1.1.0_04_2013
Te
ch
ni
ca
l
X-
Ty
pe
22
0V
6
0H
z
V
Technical Data Upflow Units X Type - 2
Performance Data
Cooling Capacity (1)
Ambient
Air On
25°C
30°C
35°C
40°C
(DB°C/%RH)
TC (kW)
SC (kW)
TC (kW)
SC (kW)
TC (kW)
SC (kW)
TC (kW)
SC (kW)
V8X-EZRE-2 / CR16
22/50
9.1
8.8
9.1
8.8
9.1
8.8
8.7
8.5
24/45
9.4
9.3
9.4
9.3
9.4
9.3
9.0
9.0
26/40
9.7
9.7
9.7
9.7
9.7
9.7
9.3
9.3
V10X-EZRE-2 / CR16
22/50
10.1
10.1
10.1
10.1
10.0
10.0
9.5
9.5
24/45
10.4
10.4
10.4
10.4
10.3
10.3
9.8
9.8
26/40
10.8
10.8
10.8
10.8
10.6
10.6
10.1
10.1
V13X-EZRE-2 / CR22
22/50
13.1
12.2
13.1
12.2
13.0
12.2
12.4
11.8
24/45
13.5
13.2
13.5
13.2
13.4
13.2
12.8
12.8
26/40
13.9
13.9
13.9
13.9
13.8
13.8
13.2
13.2
V15X-EZRE-2 / CR22
22/50
15.8
14.9
15.8
14.9
15.5
14.7
14.7
14.3
24/45
16.3
15.8
16.3
15.8
15.9
15.5
15.2
15.1
26/40
16.8
16.8
16.8
16.8
16.4
16.4
15.6
15.6
V17X-EZRE-2 / CR30
22/50
19.0
16.9
19.0
16.9
18.7
16.8
17.8
16.3
24/45
19.5
18.1
19.5
18.1
19.2
17.9
18.3
17.4
26/40
20.0
19.4
20.0
19.4
19.6
19.2
18.8
18.7
V20X2-EZRE-2 / CR30
22/50
23.7
21.5
23.7
21.5
22.8
21.0
21.6
20.3
24/45
24.4
23.2
24.4
23.2
23.4
22.6
22.2
21.9
26/40
25.0
24.7
25.0
24.7
24.0
24.0
22.8
22.8
V22X2-EZRE-2 / CR50
22/50
24.3
23.2
24.3
23.2
24.3
23.2
23.3
22.6
24/45
25.1
24.9
25.1
24.9
25.1
24.9
24.1
24.1
26/40
25.8
25.8
25.8
25.8
25.8
25.8
24.8
24.8
V26X2-EZRE-2 / CR50
22/50
26.2
24.0
26.2
24.0
26.2
24.0
25.0
23.3
24/45
27.0
25.8
27.0
25.8
27.0
25.8
25.8
25.0
26/40
27.9
27.5
27.9
27.5
27.9
27.5
26.6
26.6
V28X-EZRE-2 / CR50
22/50
26.6
26.6
26.6
26.6
26.6
26.6
25.4
25.4
24/45
27.7
27.7
27.7
27.7
27.7
27.7
26.4
26.4
26/40
28.8
28.8
28.8
28.8
28.7
28.7
27.5
27.5
V28X2-EZRE-2 / CR50
22/50
25.6
25.6
25.6
25.6
25.6
25.6
24.5
24.5
24/45
26.6
26.6
26.6
26.6
26.6
26.6
25.4
25.4
26/40
27.6
27.6
27.6
27.6
27.6
27.6
26.5
26.5