Easicool™ precision air conditioning, Technical data downflow units x type – Airedale EasiCool 6kW 64kW User Manual
Page 139

EasiCool™
Precision Air Conditioning
139
EasiCool Technical Manual 7535776 V1.1.0_04_2013
Te
ch
nic
al
X-T
yp
e
22
0V
6
0H
z
V
V40X-EZRE-2
V40X2-EZRE-2
V45X2-EZRE-2
Standard Condenser Match - X
CR65
CR65
CR80
Unit Data Full Function - X
(1)
Nominal Run Amps
A
157.6
156.6
167.1
Maximum Start Amps
A
414.9
323.8
330.5
Recommended Mains Fuse Size
A
200
200
200
Unit Data Cooling Only - X
(2)
Nominal Run Amps
A
78.9
77.9
88.4
Maximum Start Amps
A
336.2
245.0
251.8
Recommended Mains Fuse Size
A
100
100
100
Max Mains Incoming Cable Size
mm²
185
185
185
Mains Supply
V
220V / 3PH / 60HZ
Control Circuit
VAC
24
24
24
Evaporator Fan - Motor Per Fan
Centrifugal Forward Curved DD EC - Designed to 25Pa ESP
Maximum Electrical Input Power
(3)
kW
6.3
6.3
6.3
Full Load Amps
A
25.63
25.63
25.63
Locked Rotor Amps
A
197
197
197
Compressor - Per Compressor
Quantity x Motor Size
kW
1 x 16.07
2 x 8.26
2 x 9.19
Nominal Run Amps
A
46.72
22.9
26.6
Locked Rotor Amps
A
304
190
190
Type Of Start
Direct On Line
Standard Condenser Match - AC Motor - Per Fan
Electrical Input Power
kW
0.64
0.64
0.64
Full Load Amps
A
3.02
3.02
3.02
OPTIONAL EXTRAS
Electric Heating
Stage Of Reheat
3
3
3
Number Of Elements
12
12
12
Rating
kW
30
30
30
Current Per Phase
A
78.73
78.73
78.73
Humidifier
Capacity
kg/hr
15
15
15
Rating
kW
11.25
11.25
11.25
Full Load Amps
A
29.52
29.52
29.52
Evaporator Fan Options
Larger Fan Motor - AC Motor - Per Fan
Centrifugal Forward Curved AC - Designed to 25Pa ESP
Electrical Input Power
(3)
kW
N/A
N/A
N/A
Full Load Amps
A
N/A
N/A
N/A
Locked Rotor Amps
A
N/A
N/A
N/A
Standard Size Motor - EC Motor - Per Fan
Centrifugal Backward Curved DD EC - Designed to 25Pa ESP
Electrical Input Power
(3)
kW
2.63
2.63
2.63
Full Load Amps
A
9.8
9.8
9.8
Condenser Fan Options
Standard Condenser Motor - EC Motor - Per Fan
Electrical Input Power
kW
0.73
0.73
0.73
Full Load Amps
A
3.3
3.3
3.3
Technical Data Downflow Units X Type
Electrical Data
V40X - V45X2
Mechanical
(1)
Entering air 24°C/45% RH ambient 35°C.
(2)
Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.
(3)
With Standard forward curved fan motors; Machine weight includes a refrigerant charge.
(4)
Backward curved EC fan options quote electrical power. All other options quote shaft power.
(5)
For refrigerant charges, refer to
Unit Refrigerant Charge (kg/Circuit)
.
(6)
Based on air temperature of 15.5°C leaving the evaporator coil.
(7)
Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to
Low Pressure Hot Water
.
Electrical
(1)
Values given for full function units (incl. electric heating, humidification and matched condenser) at 7°C evaporating and 54.4°C condensing with standard
forward curved fan motors, for optional data, please contact Airedale.
(2)
Values given for Cooling only units (incl. Compressor, evaporator fan and matched condenser) at 7°C evaporating and 54.4°C condensing, for optional
data, please contact Airedale.
(3)
Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.