Technical data, Easicool™ precision air conditioning, Operating limits – Airedale EasiCool 6kW 64kW User Manual
Page 56: Important

EasiCool™
Precision Air Conditioning
56
EasiCool Technical Manual 7535776 V1.1.0_04_2013
Technical Data
Moisture Content
Operating Band
Mo
ist
ure
C
on
ten
t k
g/k
g D
ry
Air
W
et
Bu
lb
Te
mp
era
tur
e (
°C
)
Dry Bulb Temperature (°C)
40
%
60
%
70
%
80
%
90
%
20%
10%
10
15
20
25
5
0
15
18
28
10
5
0
20
25
30
35
40
10
0%
50
%
Re
lat
ive
H
um
idi
ty
En
th
alp
y a
t s
at
ur
at
ion
(J
/g
D
ry
A
ir)
●
Nominal Design Operating Condition 24°C Dry Bulb 45% RH
Operating Limits
Indoor Air Temperature
+18°C to +28°C
Indoor RH%
+40% to +55% (Based upon 24°C Dry Bulb)
Outdoor Temperature
-20°C to +48°C
IMPORTANT
Fan Power Input (Fan Gain) must be added to the room load to establish full gross cooling capacity requirements.
Fan Power Input can be found in the mechanical data sections.
Fan Power Input is taken at the operating conditions based on 25Pa ESP.