B.58 [source:]voltage:protection:under command, B.59 [source:]voltage:protection:under? query, B.62 [source:]voltage:transient command – KEPCO EL Series Electronic Load Operator Manual P/N 243-1295 Firmware Version 4.00 to 4.xx User Manual
Page 79: B.57, Source, B.58, B.59, B.60, B.61, B.62

SERIES EL 071414
B-11
B.57
[SOURce:]VOLTage:PROTection:OVER:STATe[:LEVel]? COMMAND
VOLT:PROT:OVER:STAT?
Syntax:
Short Form: [SOUR:]VOLT:PROT:OVER:STAT[:LEV]
Long Form: [SOURce:]VOLTage:PROTection:OVER:STATe[:LEVel]
where
0 (overvoltage protection error has not occurred)
Description: Indicates whether an overvoltage protection has occurred (1) or not (0).
B.58
[SOURce:]VOLTage:PROTection:UNDer COMMAND
VOLT:PROT:UND
Syntax:
Short Form: [SOUR:]VOLT:PROT:UND
Long Form: [SOURce:]VOLTage:PROTection:UNDer
where
Description: Sets undervoltage protection limit. Undervoltage protection setpoint is stored in non-volatile mem-
ory; value is restored upon power-up.
B.59
[SOURce:]VOLTage:PROTection:UNDer? QUERY
VOLT:PROT:UND?
Syntax:
Short Form: [SOUR:]VOLT:PROT:UND?
Long Form: [SOURce:]VOLTage:PROTection:UNDer?
Returns:
Description: Indicates undervoltage protection limit.
B.60
[SOURce:]VOLTage:PROTection:UNDer:STATE[:LEVel] COMMAND
VOLT:PROT:UND:STAT 0
Syntax:
Short Form: [SOUR:]VOLT:PROT:UND:STAT[:LEV] 0
Long Form: [SOURce:]VOLTage:PROTection:UNDer:STATe[:LEVel] 0
Description: Clears undervoltage protection error. This error occurs when input voltage is less than
VOLT:PROT:UND level.
B.61
[SOURce:]VOLTage:PROTection:UNDer:STATE[:LEVel]? QUERY
VOLT:PROT:UND:STAT?
Syntax:
Short Form: [SOUR:]VOLT:PROT:UND:STAT[:LEV]?
Long Form: [SOURce:]VOLTage:PROTection:UNDer:STATe[:LEVel]?
where
0 (undervoltage protection error has not occurred)
Description: Indicates whether an undervoltage protection error has occurred (1) or not (0).
B.62
[SOURce:]VOLTage:TRANsient COMMAND
VOLT:TRAN
Syntax:
Short Form: [SOUR:]VOLT:TRAN
Description: Configures a transient voltage pulse that is initiated by SYST:MODE:TRAN (see PAR. B.100).