Load cable connection – GW Instek SPD-3606 User Manual
Page 12

SETUP
23
* When setting the OVP for
channel3, select CH3 meter 
using the CH1/CH3 meter 
switch. 
CH1
CH3
5. When finished, slide the
rear panel switch to the 
“Normal” position. The 
OVP indicator on the front 
panel turns Off. 
CH3
CH2
CH1
O.V.P. SET
NORMAL
O.V.P.
SET
TRIP
O.V.P.
SET
TRIP
When OVP is 
activated.... 
The OVP activates when one 
of channel1/2/3 output 
voltage exceeds the OVP 
setting. The indicator turns red 
(tripped), and the output is 
shut Off immediately. 
O.V.P.
SET
TRIP
O.V.P.
SET
TRIP
OUTPUT
ON / OFF
OUTPUT
ON / OFF
SPD-3606 User Manual
24
Load Cable Connection
Standard 
accessory 
(GTL-104) 
1. Turn the terminal
counterclockwise and 
loose the screw. 
2. Insert the cable
terminal.
CH2
GND
0 60
V , 3A
0 30
V , 6A
2
1
3. Turn the terminal
clockwise and tighten 
the screw. 
CH2
GND
0 60
V , 3A
0 30
V , 6A
3
Banana plug
Insert the plug into the 
socket. 
CH2
GND
0 60
V , 3A
0 30
V , 6A
Wire type
When using load cables other than the attached, 
make sure they have enough current capacity for 
minimizing cable loss and load line impedance. 
Voltage drop across a wire should not excess 0.5V. 
The following list is the wire current rating at 
450A/cm
2
.
Wire size (AWG)
Maximum current (A)
20
2.5
18
4
16
6
14
10
12
16
