Pcb 186, Up down – Hired-Hand Evolution Series 1200 User Manual
Page 42
![background image](/manuals/362893/42/background.png)
Part No. 4801-5331 Rev 2-08
Evolution 1200
42 of 64
8.2
Setting Stage & Inlet Option Switches on EV1200 PCB 186 Board
NOTES
SWX4: Stages 7 & 8 Option Switch (Variable Speed or On/Off Stages)
Stages 7 & 8 are user selectable to be either Variable Speed Fan Outputs or regular On/Off Stages.
By moving the switch upward, you are selecting operation as On/Off Stages, in which case, Stages 7 & 8
will be controlled by the programmed settings of “On/Off Stages” #7 & #8 (Refer to Section 7.8).
By moving the switch downward, you are selecting operation as Variable Speed Output Stages, in which
case, Stages 7 & 8 will be controlled by the programmed settings of “Variable Stages” #1 & #2 (Refer to
Section Error! Reference source not found.). Stage 7 output will be controlled by Variable Stage #1 and
Stage 8 output by Variable Stage #2 programming.
SWX2 & SWX3: PT Unit #1 & #2 Option Switches
Each of the PT Unit Outputs (Power Trak) contains two modes of operation. This allows the EV1200 to be
used in many different applications. These selection switches allow individual selection for each of the
outputs between control of Natural Ventilation or Power Ventilation. This allows control of a variety of
different buildings from Natural Ventilation only buildings to Power Ventilated buildings and everything
in between.
SWX2: PT Unit #1 Output
Selects whether this output is controlled by the “Vent Inlet” programming (Refer to Section
Error! Reference source not found.) or by the “Natural Unit” #1 programming (Refer to Section
6.4.3).
SWX3: PT Unit #2 Output
Selects whether this output is controlled by the “Tunnel Inlet” programming (Refer to Section
Error! Reference source not found.) or by the “Natural Unit” #2 programming (Refer to Section
6.4.3).
St
ages 7 & 8:
Swit
ch Down = Variable #1 & #2
Swit
ch Up = O
n
/ O
ff
St
ages #7 & #8
PCB 186
Option Switches
P
T
Unit
#1:
Switch Down = Power Ventilation
Switch Up = Natural Ventilation
UP
DOWN
Stage number
(Use V1-V2
label over
Stages 7 & 8 if
Stages 7 & 8 are
used for
Variable
Output).
P
T
Unit
#2:
Switch Down = Power Ventilation
Switch Up = Natural Ventilation
Stages 7 & 8
Output Terminals
PT Unit #1 & #2
Output Terminals