Pump

To Power

Plug

WHT

BLK

GRN

To

Pump

To Fan

Motor

To Power

Plug

Power Jumpers







INSTRUCTIONS

1. Disconnect all electrical power to PolarCool.

(i.e. Unplug power cord).

2. Remove

cooling

pads.

3. Refer to Figure 3 at lower right. Open

electrical wiring box.

4. For Single speed pump, refer to Figure 1

below. For variable speed pump, refer to
Figure 2 below. Carefully disconnect pump
wires only from terminals. Pull wires through
conduit and out of electrical box. Unbundle
pump power cord from other cords so that
pump can be removed.

5. Disconnect water hose from pump. Keep

clamp for later use in Step 11.

























































































Tools Required

Phillips Head

Screwdriver

Small Flat Head

Screwdriver

Wire Pliers

Wire Cutter

WARNING!

Before Installing Pump, Disconnect All Electrical

Power To PolarCool!

KITS

6422-0610

/KIT PC 18" Pump Replace 120V

6422-0611

/KIT PC 18" Pump Replace 230V

6422-0612

/KIT PC 24" Pump Replace 120V

6422-0613

/KIT PC 24" Pump Replace 230V

6422-0614

/KIT PC 36" Pump Replace SS

6422-0615

/KIT PC 36" Pump Replace 120V

6422-0616

/KIT PC 36” Pump Replace 230V

6422-0617

/KIT PC 48" Pump Replace 230V

Kits include pump, mounting bracket and hardware

PUMP REPLACEMENT

Figure 2 - Variable Speed Pump

Figure 1 - Single Speed Pump

NOTE: Inside view
of PolarCool. For clarity, not
all internal parts are shown.

Electrical Box
(location may
vary from
picture)

Pump &

Bracket

Figure 3