(1)Target Temp =
77.5°
(2)Ramping:
On
(3)Target Press =
0.04 wc
(4)Ramping:
Off
(5)Tunnel Press =
0.00 wc
(6)Target Humidity < 60%
(7)Light Schedule
(8)Feed Schedule
6.2 Target
Conditions
The current target environmental conditions of the building are shown below. The specific Target
Conditions screen features and setting options will depend on whether Optimum Mode is ON or OFF.
Examples and details for both the Standard screen and Optimum screen are shown in the following two
subsections.
6.2.1 Target Conditions - Standard Screen With Optimum Mode OFF
(1) Target Temp - This is the desired temperature of
the building.
(2) Ramping – Indicates if ramping of the Target
Temperature is turned On or Off. You are also
allowed to turn the temperature ramping on or
off in the program set up screen. You use the
Navigator to reach the Program Setup screen and
then navigate down to "Temperature Ramp" and
press enter. See Section 7.6.
(3) Target Press - This is the desired negative
pressure in the building. See Section 7.4.
(4) Ramping – Indicates if ramping for the Target
Pressure is turned on: On or Off. You are also
allowed to turn the pressure ramping on or off in
the program setup screen. See Section 7.4.
(5) Tunnel Pressure – Indicates the desired negative
pressure in the building while in the Tunnel
Mode. See Section 7.4.
(6) Target Humidity – The desired humidity inside
the building (PCB186-J14 Humidity Sensor) is
less than this set number. For every percentage
increase in humidity over the set %, the timer
percentage will increase.
EXAMPLE:
Target Humidity < 65%
Timer Percentage is set to 20% of 5 minutes.
If Humidity in building is at 70%, the timer
percentage will be at 25%.
NOTE: This only affects the variable timer %.
Min1% and Min2% are unaffected.
(7) Light Schedule – View Light Clock Setup. See
Section 7.12.
(8) Feed Schedule – View Feed Clock Setup. See
Section 7.11.