Part No. 4801-5331 Rev 2-08

Evolution 1200

33 of 64

(1) ON/OFF Stage 1 (Target: 70.0

°)


(2) Sensor(s)= -----------1
(3) Mode = Cool Evap
(4) Timer = None

(5) On/Point = 70.4

°

(6) OffPoint = 70.0

°

**VARIABLE STAGES**((1)Target: 77.5°)

(2)# (3)SENSORS (4)MODE (5)MaxON (6)MinON (7)CURVE (8)TIME

1

-------1 Light

Ramp

2

-------1 Cstir 76.2° 74.0° Fan 4 None

NOTE: Highlight and press ENTER
to bring up details on each stage.

(4) Mode – This mode column will indicate how the stage is Programmed to operate.

(OFF) Disables stage from operating during automatic operation.
(Heat) Heat Mode: This method of heating only operates when the curtains are in the closed

position and the operating sensor is below the on temperature.

(CSTIR) Cool Stir Mode: This mode setting allows the cool stage to run whether the main curtain

is open or closed.

(CNEG) Cool Negative: Method of ventilation where air is drawn out of the building by fans,

creating a negative static pressure which draws air into the house from all openings at a
even pace. Will not operate in Tunnel or Nat.

(CNEGT) Cool Negative Tunnel: A combination of the Cool Negative and the Cool Tunnel

Modes.

(CTUN) Cool Tunnel: Only operate during Tunnel operation with one exception being set as a

minimum ventilation timer which will allow the stage to operate on a timer only, in
minimum or power ventilation.

(LIGHT) The LIGHT Mode: See Section 7.12.
(FEED) The FEED mode: See Section 7.11.
(CEVAP) Cool Evaporative mode See Section 7.10.6
(CHEAT) Cooler Heat mode: Heat stage for the Cooler.
(CCOOL) Cooler Cool mode: Cool stage for the Cooler.

(5&6) ON/OFF –The ON column will indicate the current setting for the onpoint temperature of the stage.

Set this to the temperature you would like for the stage to come on at. The OFF column will
indicate the current setting for the offpoint temperature of the stage. Set this to the temperature you
would like for the stage to turn off at.

(7) TIMER – None, Min1, Min2, Var, Cool, OPT1-OPT8: This Timer column will indicate what type of

timer you want the stage to operate from. If the stage doesn't need a timer then you must have this
setting to none.

7.8.1 On/Off Stage Details

(1) ON/OFF STAGE # – Stage

number.

(2) Sensor(s) Sensors used.
(3) Mode –See Section 7.8.
(4) Timer –See Section 7.8.
(5) On/Point See Section 7.8.
(6) OffPoint See Section 7.8.

7.9

Variable Stage Outputs

(1) Target - Displays

the target
temperature.

(2) # - Identifies the

Variable Stage
unit below.

(3) Sensors - The

selected sensor(s) to operate. Active
sensors will be indicated by a number starting
with #1 from right to left. Inactive sensors will

be

indicated by a - or hyphen. When "outside-" is
displayed, outside sensor is active. To use sensors 1,2 and 3, "-----321" should be displayed.

(4) Mode - CSTIR, CNEG, CNEGT, CTUN, LIGHT. NOTE: This mode column will indicate how the

stage is Programmed. You are allowed to set any stage at any of these modes. When the stage is
used to control lighting then you must set the mode and curve to Light.