7 natural ventilation properties, 11 feed clock setup, 1 feed clock schedules – Hired-Hand Evolution Series 1200 User Manual
Page 37
Part No. 4801-5331 Rev 2-08
Evolution 1200
37 of 64
**FEED CLOCK SETUP**
(1)Feed Cycle Light Override = No
(2)Feed Cycle Light Intensity = 25%
(3)Growout Schedules Used by Ramp = 1-4
(4)Schedule (5)START DAY
1
1
2
7
3
14
4
21
5
28
(1)Feed Schedule: 1
(2)Start Day = 1
(3)Number of On/Off Cycles = 3
(4)Days in Operation = Every Day
(5)Choose Days = SMTWTFS
(6)CYCLE (6)START (7)RUNTIME
1 12:00a 1:30
2 5:00a 1:00
3 12:00p 1:00
** Natural Ventilation Properties **
The Natural Ventilation Stages typically
operate sidewalls. The following are some
additional properties:
(1)Time Override:
Allow to Operate Always
Time falls between 5:00p - 5:00a
(2)Growout Day Override:
Allow to Operate Only While
Growout Day > 7
(3)Outside Temperature Override
Allow to Operate Always
Outside Temperature > Target +10.2°
7.10.7 Natural Ventilation Properties
(1) Time Override - When set to
Only While, the Time
Override will allow the
Natural Curtain Stages to
open while the time is
between the times you set.
Otherwise when set to
Always, the time will not
affect the Natural Curtain
Stages.
(2) Growout Day Override - When
set to Only While, the
Growout Day Override will
allow the Natural Curtain
stages to operate only while
the growout day is greater
than the day you set. Otherwise when set to Always, the day of growout will not affect the
stages.
(3) Outside Temperature Override - When set to Only While, the Outside Temperature Override will
allow the stages to open only while the outside temperature is greater than the target plus or minus
the desired setting. Otherwise when set to Always, the outside temperature will not affect the
stages.
7.11 Feed Clock Setup
The Feed Clock Setup establishes the parameters necessary to enable automatic feed control functions.
(1) Feed Cycle Light Override – Turns the
lights to a set intensity while running the feed
program.
(2) Feed Cycle Light Intensity – Sets the light
intensity percentage to occur during the feed
cycle.
(3) Growout Schedules Used by Ramp - Set
the number of growout schedules up to five.
(4) Schedule – The schedule number will
automatically be set by Evolution.
(5) Start Day - Displays the growout day on
which the selected schedule will start. The Start Day is settable on the Schedule screen.
7.11.1 Feed Clock Schedules
The Feed Clock Schedules screen contains options for the feeding period daily cycles, skip days and
runtimes.
Select the individual schedules in the Feed Clock Setup screen.
This screen is also available from the Target Conditions screen as described in Section 6.2.
(1) Feed Schedule – The feed schedule selected
from the Feed Clock Setup screen will
appear here.
(2) Start Day – Set the growout day in which
the specific schedule starts.
(3) Number of On/Off Cycles – Enter the
number of On/Off cycles desired (up to ten).
(4) Days in Operation – This setting is used for
special feeding cycles running the feed only
every other day if set to odd or even days.
Enter the desired Days In Operation option for operating growout days.