Davey Speedman Dual Pump Variable Speed Pump Control System User Manual

Page 55

background image

55

Danfoss FC102

Speedman parameters for use with Danfoss FC102 VSD
Recommended initialisation (via par.14-22 Operation Mode)

1. Select par.14-22 Operation Mode
2. Press [OK]
3. Select “Initialisation”
4. Press [OK]
5. Cut off the mains supply and wait until the display turns off.
6. Reconnect the mains supply - the frequency converter is now reset.
7. Change par.14-22 Operation Mode back to Normal Operation.

VACON NXL
Speedman parameters for use with Vacon NXL
(To RESET the NXL to factory setting MENU S6.3 – P63.1 [6]

Parameters

Description

DEFAULT

Speedman

Set-up

Commissioning

Date & Data

0-02

MOTOR SPEED UNIT

RPM

Hz

1-00

CONFIGURATION

OPEN LOOP

OPEN LOOP

1-03

TORQUE

CHARACTERISTICS

AUTO ENERGY

OPTIMISATION

VARIABLE

TORQUE

1-20

MOTOR POWER

DEPENDS ON PUMP SIZE

1-22

MOTOR VOLTAGE

DEPENDS ON MOTOR

1-23

MOTOR FREQUENCY

DEPENDS ON MOTOR

1-24

MOTOR CURRENT

DEPENDS ON PUMP SIZE

1-25

RATED MOTOR SPEED

DEPENDS ON MOTOR

4-14

MOTOR SPEED HIGH LIMIT

25Hz

50Hz

3-11

JOG FREQUENCY

5Hz

50Hz

3-41

RAMP UP TIME

1 Sec

3-42

RAMP DOWN TIME

5 Sec

5-12

TERMINAL 27 INPUT

RESET

[3] COAST

&RESET

INVERSE

6-10

TERMINAL 53 MIN SCALING

0.7V

0.0V

6-11

TERMINAL 53 MAX

SCALING

10V

10V

5-40 [0]

ITEM [0] - RELAY 1

FUNCTION

[9] ALARM

[9] ALARM

5-40 [1]

ITEM [1] - RELAY 2

FUNCTION

RUNNING

[9] ALARM

Param-

eters

Description

DEFAULT

Speedman Set-up

Commission

ing Date &

Data

Startup

Wizard

STANDARD

STANDARD

P.2.1.3

ACCELERATION TIME 1

1.0

1.0 SEC

P.2.1.4

DECELERATION

1.0

1.0 SEC

P.2.1.5

CURRENT LIMIT

As per Nameplate

+10%

P.2.1.6

MOTOR VOLTAGE

400V

As per Nameplate

P.2.1.7

MOTOR FREQUENCY

50Hz

As per Nameplate

P.2.1.8

RATED MOTOR SPEED

1440

As per Nameplate

P.2.1.9

MOTOR CURRENT

Nominal Motor Current

As per Nameplate

P.2.1.19

D IN3 FUNCTION

[6]

Fault Reset [4]

P.2.2.0

A I1 SIGNAL RANGE

0-10V [3]

0-100% (0-10V0 [3]

P.2.7.4

OUTPUT PHASE

SUPERVISION

RELAY OUTPUT 1

FAULT