Pump definitions jockey pump – Davey Speedman Dual Pump Variable Speed Pump Control System User Manual
Page 36
![background image](/manuals/361866/36/background.png)
36
Flow Type
The “Flow Type” setting allows the user to select how the flow rate is determined.
Options are Calculated, Scaled AnInp2 or Digital Pulse.
•
“Calculated” uses the flow rate setting “Pump Flow Rate” in the settings menus to calculate the current
Flow Rate.
•
“Scaled AnInp2” uses an analogue sensor (ether current-loop or variable voltage ) to determine the
current Flow Rate.
•
Digital Pulse uses a compatible digital output flow meter to determine the current Flow Rate.
Manual Run
Serial Comms selects how the onboard RS-485 serial port is used.
•
Output Cont Data options is a data logging option that allows the pump station
to be remotely or locally logged.
•
Modbus Protocol allows modbus compatible interfaces to monitor and adjust values during operation.
Duty
If a pump is defined as Duty, then the relevant pump will be available for operation.
The number of pumps visible in these screens is determined by the “number of pumps” screen within
the CONFIGURE menu.
If pump 1 is defined as Jockey the “JOCKEY PUMP” menu will become visible.
Flow Type
Calculated
Manual Run
Input or P_But’n
Pump 1
Duty
Pump 1
selection
Duty, Jockey
Duty
Pump 2
selection
Duty
Duty
PUMP DEFINITIONS
JOCKEY PUMP
Jockey Pump Mode
selection
DOL, Main VSD, Separate VSD
Main VSD
JP Cut In Pressure
% of JP
Setpoint
0 - 9999
250
JP Cut Out Pres
Unitless
0 - 9999
300
JP Set Point
Unitless
0 - 9999
300
JP Flow Rate
/Sec
0 - 9999
50
JP Response Rate
%
0.1 - 100.0
3.0
JP Acceleration
%/second
1 - 100
20
JP Standby Test
selection
Off,Boost,Flow Switch, Flow Rate
Boost
JP Standby Boost
% of JP
Setpoint
5 - 250
5
JP Stdby FlowMin
/Sec
0 - 250
5
JP Run On Time
seconds
0 - 999
1
JP Restart Delay
seconds
0 - 999
0
JP Use Main SP
selection
Yes, No
No