Flow Type

The “Flow Type” setting allows the user to select how the flow rate is determined.
Options are Calculated, Scaled AnInp2 or Digital Pulse.

“Calculated” uses the flow rate setting “Pump Flow Rate” in the settings menus to calculate the current

Flow Rate.

“Scaled AnInp2” uses an analogue sensor (ether current-loop or variable voltage ) to determine the

current Flow Rate.

Digital Pulse uses a compatible digital output flow meter to determine the current Flow Rate.

Manual Run

Serial Comms selects how the onboard RS-485 serial port is used.

Output Cont Data options is a data logging option that allows the pump station

to be remotely or locally logged.

Modbus Protocol allows modbus compatible interfaces to monitor and adjust values during operation.

Duty

If a pump is defined as Duty, then the relevant pump will be available for operation.

The number of pumps visible in these screens is determined by the “number of pumps” screen within
the CONFIGURE menu.

If pump 1 is defined as Jockey the “JOCKEY PUMP” menu will become visible.

Flow Type
Calculated

Manual Run
Input or P_But’n

Pump 1
Duty

Pump 1

selection

Duty, Jockey

Duty

Pump 2

selection

Duty

Duty

PUMP DEFINITIONS

JOCKEY PUMP

Jockey Pump Mode

selection

DOL, Main VSD, Separate VSD

Main VSD

JP Cut In Pressure

% of JP

Setpoint

0 - 9999

250

JP Cut Out Pres

Unitless

0 - 9999

300

JP Set Point

Unitless

0 - 9999

300

JP Flow Rate

/Sec

0 - 9999

50

JP Response Rate

%

0.1 - 100.0

3.0

JP Acceleration

%/second

1 - 100

20

JP Standby Test

selection

Off,Boost,Flow Switch, Flow Rate

Boost

JP Standby Boost

% of JP

Setpoint

5 - 250

5

JP Stdby FlowMin

/Sec

0 - 250

5

JP Run On Time

seconds

0 - 999

1

JP Restart Delay

seconds

0 - 999

0

JP Use Main SP

selection

Yes, No

No