PUMP DATA LOG

NOTE: The FAULT HISTORY menu is cleared when the system is first powered up.

If there is a problem with the clock or the clock hasn’t been initialised correctly then “RTC ERROR” will appear
along with the fault. See “Set Time and Date” in the CONFIGURE menu for more details.

“Pump 1 - 2 Shutdown” signifies that the corresponding “Pump protect 1-6” input has been activated for the
period of the input delay time.

A HIGH TEMPERATURE fault is recorded when the temperature rises above 60 degrees C. This fault will
continue to be updated if the temperature continues to
rise along with the time and date that the highest temperature was recorded.
This fault stops being updated when the temperature drops below 55 degrees C.
After this a new fault will appear if the temperature rises above 60 degrees C.

“Auto Reboot” denotes that the Speedman has automatically restarted due to an internal reset, whereas
“Power Failure” records that the Speedman has recovered from a power supply problem.

The FAULT HISTORY menu is always accessible (no access code is required)

Flow Total

The Totalised Flow is displayed. It is calculated from the flow rate input and can be
derived from a flow meter or the calculated “Flow Rate” figure set in the Pump Flow
Rate Screen in SETTINGS.

If the Speedman uses Flow Rate/Sec to calculate “Total Flow”, the value is based on the Average Flow input
into the system. The accuracy is dependent on the average flow information and is most often in the order of
accuracy of ±5%. Site variations such as suction pressure can affect the accuracy of this figure. The FLOW
TOTAL is updated every 1 minute and can be reset by pressing ENTER.

Average Flow Rate

The Average flow is calculated over the period since the last reset. The flow units are
derived either from a calculated flow or the input from a flow meter.
To reset press ENTER.

Flow Total
XXXXXXX

Average Flow Rate
XXXX /Sec

F1 Hi Temp 69C
01/04/08 11:51

Flow Total

Unitless

0 - 9999999

display

Average Flow Rate

/Sec

0 - 9999

display

Average Pressure

Unitless

0 - 9999

display

Highest Pressure

Unitless

0 – 9999

display

Hours Run 1

hours

0 - 65535

display

Hours Run 2

hours

0 - 65535

display

Pump Starts 1

number

0 - 65535

display

Pump Starts 2

number

0 - 65535

display

Pump Starts Last Hr

number

0 - 65535

display

Analogue Input 1

%

0.00 - 100.00

display

Analogue Input 2

%

0.00 - 100.00

display

Analogue Output 1

%

0.00 - 100.00

display

Analogue Output 2

%

0.00 - 100.00

display

Digital Input State M

1 - 8

X for Active

display

Digital Output State

1 - 2

X for Active

display

PID Error

%

0.00 - 100.00

display

Curr & max retry

number

0-20 0-20

display

Temperature

degrees C

0 - 999

display

Modbus monitor

Rx, Tx, Err

0-9999

display