Davey Speedman Dual Pump Variable Speed Pump Control System User Manual

Page 40

background image

40

Shutdown Fault

This output is used to indicate that there has been an event that has shut down the system. This can

be a High or Low-Pressure Shutdown, No Flow Shutdown or VSD Shutdown.

Low Pressure Fault

A shutdown based on a Low Pressure Shutdown.

High Pressure Fault

A shutdown based on a High Pressure Shutdown.

Any Alarm

If there are any conditions that MAY cause a shut down (Eg. Low or High Pressure) or Fault Re-starts

active this output will activate.

Pump 1-2 Run

Activates when the relevant pump is running.

Pump 1-2 Shutdown

Pump 1-2 shutdown on individual pump protection activation.

System Paused

Either “system pause” or “system pause JP run” inputs have been activated

Any Pump Shutdown

Any pump shutdown will activate the relay.

Digital Output Options

No

Option

Delay

1

Shutdown Fault

As per delay timers

2

Low Pressure Fault

As per delay timers

3

High Pressure Fault

As per delay timers

4

Any Alarm

Instantaneous

5

Pump 1 Run

Instantaneous

6

Pump 2 Run

Instantaneous

7

Pump 1 Fault

As per Input Delay Timer

8

Pump 2 Fault

As per Input Delay Timer

9

System Paused

Instantaneous

10

Any Pump Shutdown

As per Input Delay Timer

11

Any Pump Running

Instantaneous

12

No Flow Shutdown

As per Input Delay Timer

13

VFD Fault

Instantaneous

14

Pressure Trip 1

As per Press Trip delay timers

15

Pressure Trip 2

As per Press Trip delay timer

16

Alternate Trip

Instantaneous

17

Flow trip

As per Flow trip delay timers

18

Jockey Pump Run

Instantaneous

19

Aux Output 1

Instantaneous

20

Aux Output 2

Instantaneous

21

Aux Output 3

Instantaneous

22

SP 1 Output

Instantaneous

23

SP 2 Output

Instantaneous

24

SP 3 Output

Instantaneous

25

SP 4 Output

Instantaneous

26

SP 5 Output

Instantaneous

27

SP 6 Output

Instantaneous

28

SP 7 Output

Instantaneous

29

SP 8 Output

Instantaneous