Flow Trip High Delay

Delays the deactivation of the relevant Speedman Output relay if programmed
for Flow Trip. This delay timer is relevant for the High Flow Trip setting.

The screens “Flow Trip Low Delay” and “Flow Trip High Delay” are only visible if an output is set as “flow trip”
in the OUTPUTS menu.

Stop Time (24hr) & Start Time (24hr)

The “Stop Time” and “Start Time” option allows a period of time to be set
where the system will be paused.

For Example:
1.

Stop Time: 15:00 - Start Time: 16:00

The system pauses at 3:00 pm each day for 1 hour.
2.

Stop Time: 23:00 – Start Time: 6:00

The system pauses at 11:00 pm each day and starts again at 6:00 am the next day.

The “Stop Time” and “Start Time” requires the current time and date be set correctly in the configure menu.

Operating Mode

Select the Control Parameter relevant to the operation.
The options are:

Pressure Control

Level Control

When the relevant selection is made the menu screens will change to reflect the control parameters.

Flow Trip Hi Dly
XXX Seconds

Stop Time (24hr)
XX:XX (hh:m)

Start Time (24hr)
XX:XX (hh:m)

Operating Mode
Pressure

CONFIGURE

Operating Mode

selection

Pressure, Level, Flowrate, Temperature

Pressure

Level Mode

selection

Std An:Tank Fill, Std An:TankEmpty, Rev

An:Tank Fill, Rev An:TankEmpty

Std An:Tank

Number of pumps

number

1 - 2

1

Min Freq Mode

selection

Fixed, Calculated

Fixed

Press Decimal

number

0 – 3

0

Flow Decimal

number

0 – 3

0

Transducer Zero

Unitless

0 - 9999

Adjust Pressure

Unitless

0 - 10000

Averaging

number

0 - 50

5

Flow Meter Zero

/Sec

0 - 9999

Adjust Flow

/Sec

0 - 10000

Backup Pres Zero

Unitless

0 - 9999

0

Adjust Backup Pr

Unitless

0 - 9999

0

Scale An output 2

Number

100 – 10000

1000

JP Fallback

selection

On. Off

Off

Standby Test

selection

Boost, Flow Switch, Flow Rate

Boost

Set Time/Date

selection

00:00 2000 Jan 1 -23:59 2099 Dec 31.

00:00 2000 Jan 1

Operating System

selection

Lead VFD Lag

Friction Loss Calc

selection

Linear, Exponential

Linear

Access Code

number

Off, 0 - 250

21

Serial Comms

selection

Output Cont Data, Modbus Protocol

Modbus Protocol

Modbus Address

number

1 - 31

1

Flow Sensing

selection

Calculated, Scaled AnInp2, Digital Pulse

Calculated

Manual Run

selection

Input or P_But’n, Input Only

Input or P_But’n