Configure – Davey Speedman Dual Pump Variable Speed Pump Control System User Manual
Page 31
![background image](/manuals/361866/31/background.png)
31
Flow Trip High Delay
Delays the deactivation of the relevant Speedman Output relay if programmed
for Flow Trip. This delay timer is relevant for the High Flow Trip setting.
The screens “Flow Trip Low Delay” and “Flow Trip High Delay” are only visible if an output is set as “flow trip”
in the OUTPUTS menu.
Stop Time (24hr) & Start Time (24hr)
The “Stop Time” and “Start Time” option allows a period of time to be set
where the system will be paused.
For Example:
1.
Stop Time: 15:00 - Start Time: 16:00
The system pauses at 3:00 pm each day for 1 hour.
2.
Stop Time: 23:00 – Start Time: 6:00
The system pauses at 11:00 pm each day and starts again at 6:00 am the next day.
The “Stop Time” and “Start Time” requires the current time and date be set correctly in the configure menu.
Operating Mode
Select the Control Parameter relevant to the operation.
The options are:
•
Pressure Control
•
Level Control
When the relevant selection is made the menu screens will change to reflect the control parameters.
Flow Trip Hi Dly
XXX Seconds
Stop Time (24hr)
XX:XX (hh:m)
Start Time (24hr)
XX:XX (hh:m)
Operating Mode
Pressure
CONFIGURE
Operating Mode
selection
Pressure, Level, Flowrate, Temperature
Pressure
Level Mode
selection
Std An:Tank Fill, Std An:TankEmpty, Rev
An:Tank Fill, Rev An:TankEmpty
Std An:Tank
Number of pumps
number
1 - 2
1
Min Freq Mode
selection
Fixed, Calculated
Fixed
Press Decimal
number
0 – 3
0
Flow Decimal
number
0 – 3
0
Transducer Zero
Unitless
0 - 9999
Adjust Pressure
Unitless
0 - 10000
Averaging
number
0 - 50
5
Flow Meter Zero
/Sec
0 - 9999
Adjust Flow
/Sec
0 - 10000
Backup Pres Zero
Unitless
0 - 9999
0
Adjust Backup Pr
Unitless
0 - 9999
0
Scale An output 2
Number
100 – 10000
1000
JP Fallback
selection
On. Off
Off
Standby Test
selection
Boost, Flow Switch, Flow Rate
Boost
Set Time/Date
selection
00:00 2000 Jan 1 -23:59 2099 Dec 31.
00:00 2000 Jan 1
Operating System
selection
Lead VFD Lag
Friction Loss Calc
selection
Linear, Exponential
Linear
Access Code
number
Off, 0 - 250
21
Serial Comms
selection
Output Cont Data, Modbus Protocol
Modbus Protocol
Modbus Address
number
1 - 31
1
Flow Sensing
selection
Calculated, Scaled AnInp2, Digital Pulse
Calculated
Manual Run
selection
Input or P_But’n, Input Only
Input or P_But’n