Davey Speedman Dual Pump Variable Speed Pump Control System User Manual
Page 18
![background image](/manuals/361866/18/background.png)
18
*
All of these menus are not visible unless Pump 1 is configured to be a Jockey Pump
1
Menu only visible if the JP Standby Test mode is set to the matching function.
2
Appears when Jockey Pump Mode is set to DOL
3
When Jockey Pump Mode is set to DOL this optional has no function and will not be visible
4
Not visible when JP Use Main SP) Set Point) is set to YES
Sub Menu
Units
Range
Defaults
JOCKEY PUMP
*
Jockey Pump Mode
selection
Main VFD, Separate
VFD, DOL
Main VFD
*
JP Cut In Pressure
% of JP Setpoint
0 - 9999
83.3
2
JP Cut Out Pres
Unitless
0 - 9999
300
* 3
JP Set Point
Unitless
0 - 9999
300
*
JP Flow Rate
/Sec
0 - 9999
50
* 3
JP Response Rate
%
0.1 - 100.0
3.0
*
JP Acceleration
%/second
1 - 100
20
* 3
JP Standby Test
selection
Off,Boost,Flow Switch,
Flow Rate
Boost
* 1 3
JP Standby Boost
% of JP Setpoint
5 - 250
6.6
* 1 3
JP Stdby FlowMin
/Sec
0 - 250
5
*
JP Run On Time
seconds
0 - 999
1
*
JP Restart Delay
seconds
0 - 999
0
* 3
JP Use Main SP
selection
Yes, No
No
* 3
JP Min Frequency
%
0.0 - 100.0
10
* 3
JP ErrorCorr’t (I
seconds
Off, 0.1- 100.0
15
* 3
JP OverShtElim (D
%
Off, 0.01 - 50.00
4
Sub Menu
Units
Range
Defaults
TIME OF DAY SP
Set Point 2 Time
time
Disabled, 00:00 - 23:59
Disabled
Set Point 3 Time
time
Disabled, 00:00 - 23:59
Disabled
Set Point 4 Time
time
Disabled, 00:00 - 23:59
Disabled
Set Point 5 Time
time
Disabled, 00:00 - 23:59
Disabled
Set Point 6 Time
time
Disabled, 00:00 - 23:59
Disabled
Set Point 7 Time
time
Disabled, 00:00 - 23:59
Disabled
Set Point 8 Time
time
Disabled, 00:00 - 23:59
Disabled