18

*

All of these menus are not visible unless Pump 1 is configured to be a Jockey Pump

1

Menu only visible if the JP Standby Test mode is set to the matching function.

2

Appears when Jockey Pump Mode is set to DOL

3

When Jockey Pump Mode is set to DOL this optional has no function and will not be visible

4

Not visible when JP Use Main SP) Set Point) is set to YES

Sub Menu

Units

Range

Defaults

JOCKEY PUMP

*

Jockey Pump Mode

selection

Main VFD, Separate

VFD, DOL

Main VFD

*

JP Cut In Pressure

% of JP Setpoint

0 - 9999

83.3

2

JP Cut Out Pres

Unitless

0 - 9999

300

* 3

JP Set Point

Unitless

0 - 9999

300

*

JP Flow Rate

/Sec

0 - 9999

50

* 3

JP Response Rate

%

0.1 - 100.0

3.0

*

JP Acceleration

%/second

1 - 100

20

* 3

JP Standby Test

selection

Off,Boost,Flow Switch,

Flow Rate

Boost

* 1 3

JP Standby Boost

% of JP Setpoint

5 - 250

6.6

* 1 3

JP Stdby FlowMin

/Sec

0 - 250

5

*

JP Run On Time

seconds

0 - 999

1

*

JP Restart Delay

seconds

0 - 999

0

* 3

JP Use Main SP

selection

Yes, No

No

* 3

JP Min Frequency

%

0.0 - 100.0

10

* 3

JP ErrorCorr’t (I

seconds

Off, 0.1- 100.0

15

* 3

JP OverShtElim (D

%

Off, 0.01 - 50.00

4

Sub Menu

Units

Range

Defaults

TIME OF DAY SP

Set Point 2 Time

time

Disabled, 00:00 - 23:59

Disabled

Set Point 3 Time

time

Disabled, 00:00 - 23:59

Disabled

Set Point 4 Time

time

Disabled, 00:00 - 23:59

Disabled

Set Point 5 Time

time

Disabled, 00:00 - 23:59

Disabled

Set Point 6 Time

time

Disabled, 00:00 - 23:59

Disabled

Set Point 7 Time

time

Disabled, 00:00 - 23:59

Disabled

Set Point 8 Time

time

Disabled, 00:00 - 23:59

Disabled