Any Pump Running

Any pump running will activate the relay.

No Flow Shutdown

The No Flow Shutdown action is active.

VSD Fault

Output is on when the VSD is being tested or the VSD has shutdown.

Pressure Trip 1

When the system pressure reaches the nominated Pressure Trip 1 Low and High, this relay will

energise or de-energise. See Pressure Trip in SETTINGS.

Pressure Trip 2

When the system pressure reaches the nominated Pressure Trip 2 Low and High, this relay will

energise or de-energise. See Pressure Trip in SETTINGS.

Alternate Trip

Each time the system shuts down the energized state of the relay will change. E.g. If the relay on one

cycle is closed during operation then the next cycle this relay will be open.

The relay will change on the following: - Low Pressure Shutdown, High Pressure Shutdown, No Flow

Shutdown and VSD Shutdown.

Flow Trip

When the system flow reaches the nominated Flow Trip points Low or High, this relay will energise or

de-energise. See Flow Trip in SETTINGS.

Aux Outputs 1 - 3

Any output can be set to be an auxiliary output. Setting an output to become an auxiliary output allows

the Speedman to use an input to turn on a Digital Output. To do this the input has to be set up to be

an Auxiliary input. There are three auxiliary functions available.

Aux Input 1 operates Aux Output 1

Aux Input 2 operates Aux Output 2

Aux Input 2 operates Aux Output 3

Set Point Output 1-8 (SP 1-8 Output)

Outputs are activated depending on which set point is the current set point. The current Set Point can

be set by ether configuring an input or setting a time of day event.

*

RELAY RATINGS

The relays are rated at 5 amp 250VAC. Consideration of inrush current, inductive loads and cycling

must be taken into account when applying current to these relays.

Output Matrix below

INPUT

DEFAULT SETTINGS

Program Input 1

VFD Fault

Program Input 2

No Flow

Program Input 3

Pump 1 Manual Run

Program Input 4

Pump 1 Stop

Program Input 5

Not selected

Program Input 6

Not selected

Program Input 7

Reset

Program Input 8

Soft Pause

Analogue Input 1

Pressure

Analogue Input 2

None

INPUTS