Davey Speedman Dual Pump Variable Speed Pump Control System User Manual
Page 14

14
*
These menus are related to other settings. They are not visible unless related settings are enabled
*1
“Standby Test Time” is shown depending on the setting of “Standby Test” in the CONFIGURE Menu.
*2
“Boost Hold Time” is shown in pressure mode when “Standby Test” (in CONFIGURE Menu) is set to
Boost.
*3
If “Stop Time” is before “Start Time” then the Backup will run through midnight. Start Time is hidden if
Stop Time is disabled.
*4
“Fallback Delay” is shown if “JP Fallback” setting is “On” in the CONFIGURE Menu.
Sub Menu
Units
Range
Defaults
TIMING
Lo Press Delay
seconds
Off,
0 - 250
120
Hi Press Delay
seconds
Off,
0 - 250
4
In Delay Timer
seconds
0 - 999
4
Out Delay Timer
seconds
0 - 999
1
Restart Delay
seconds
0 - 999
0
*1
Standby Test Time
seconds
0 - 999
10
*4
Fallback Delay
seconds
0 - 999
10
*2
Boost Hold Time
seconds
Off,
1 - 250
15
Pump Fault Timer
seconds
0 - 250
10
No Flow Delay
seconds
0-250
10
I/P Delay Timer
seconds
0 - 999
120
*
Press Trip Low Delay
seconds
0 - 999
0
*
Press Trip High Delay
seconds
0 - 999
0
*
Flow Trip Low Delay
seconds
0 - 999
0
*
Flow Trip High Delay
seconds
0 - 999
0
*3
Stop Time (24hr)
HH:MM
Disabled, 0:00 -> 23:59
Disabled
*3
Start Time (24hr)
HH:MM
0:01 -> 00:00
0