Sub Menu

Units

Range

Defaults

CONFIGURE

Operating Mode

selection

Pressure, Level,

Pressure

*1

Level Mode

selection Std An:Tank Fill, Std An:TankEmpty, Rev

An:Tank Fill, Rev An:TankEmpty

Std An:Tank

Number of pumps

number

1 – 2

1

Min Freq Mode

selection

Fixed, Calculated

Fixed

Press Decimal

number

0 – 3

0

Flow Decimal

number

0 – 3

0

*2

Transducer Zero

Unitless

0 - 9999

*3

*2

Adjust Pressure

Unitless

0 - 10000

*3

Averaging

number

Disabled, 1 - 50

5

*4

Flow Meter Zero

/Sec

0 - 9999

0

*4

Adjust Flow

/Sec

0 - 10000

1000

*9

Backup Pres Zero

Unitless

0 - 9999

0

*9

Adjust Backup Pr

Unitless

0 - 9999

0

*5

Scale An output 2

number

100 – 10000

1000

JP Fallback

selection

On. Off

Off

*6

Standby Test

selection

Boost, Flow Switch, Flow Rate, Off

Boost

*8

Fallback Test

selection

Flow Switch, Flow Rate

Flow Rate

Set Time/Date

selection

00:00 2000 Jan 1 -23:59 2099 Dec 31.

00:00 2000 Jan 1

Operating System

selection

Lead VSD Lag

Lead VFD Lag

*6

Friction Loss Calc

selection

Linear, Exponential

Linear

*7

Access Code

number

Off, 0 - 250

21

Serial Comms

selection

Output Cont Data, Modbus Protocol

Modbus Protocol

Modbus Address

number

1 - 31

1

Flow Sensing

selection Calculated, Scaled AnInp2, Digital Pulse

Calculated

Manual Run

selection

Input or P_But’n, Input Only

Input or P_But’n

*

These menus are related to other settings. They are not visible unless related settings are enabled

*1

Only shown if Operating Mode is set to Level.

*2

These menus show a value that is decoupled from the value that you are changing. Thus one press up

and one press down may not corresponded to +1 or -1 change in value.

*3

These settings are by default setup for a 4-20ma sensor with the range of 0-25bar (2500 kpa).

However it is still highly recommended that you calibrate the Speedman for your sensor.

*4

These menus are only visible when one of the Analogue inputs is configured as a flow meter.

*5

Menu hidden when Analogue output 2 is configured as VSD speed.

*6

Menu hidden when in level mode.

*7

The Access Code allows you to change the access code and also determine which features require

you to enter an access code.

*8

Menu hidden unless “JP Fallback” is set to “On” in the CONFIGURE Menu.

*9

Menu hidden unless “Analogue Input 2” is set to “Backup Pressure” in the CONFIGURE Menu.

*

Whether or not these options are shown depend on how many pumps are configured in the Configuration Menu.

Sub Menu

Units

Range

Defaults

PUMP DEFINITIONS

Pump 1

selection

Duty,Jockey

Duty

*

Pump 2

selection

Duty

Duty