Davey Speedman Dual Pump Variable Speed Pump Control System User Manual
Page 15
![background image](/manuals/361866/15/background.png)
15
Sub Menu
Units
Range
Defaults
CONFIGURE
Operating Mode
selection
Pressure, Level,
Pressure
*1
Level Mode
selection Std An:Tank Fill, Std An:TankEmpty, Rev
An:Tank Fill, Rev An:TankEmpty
Std An:Tank
Number of pumps
number
1 – 2
1
Min Freq Mode
selection
Fixed, Calculated
Fixed
Press Decimal
number
0 – 3
0
Flow Decimal
number
0 – 3
0
*2
Transducer Zero
Unitless
0 - 9999
*3
*2
Adjust Pressure
Unitless
0 - 10000
*3
Averaging
number
Disabled, 1 - 50
5
*4
Flow Meter Zero
/Sec
0 - 9999
0
*4
Adjust Flow
/Sec
0 - 10000
1000
*9
Backup Pres Zero
Unitless
0 - 9999
0
*9
Adjust Backup Pr
Unitless
0 - 9999
0
*5
Scale An output 2
number
100 – 10000
1000
JP Fallback
selection
On. Off
Off
*6
Standby Test
selection
Boost, Flow Switch, Flow Rate, Off
Boost
*8
Fallback Test
selection
Flow Switch, Flow Rate
Flow Rate
Set Time/Date
selection
00:00 2000 Jan 1 -23:59 2099 Dec 31.
00:00 2000 Jan 1
Operating System
selection
Lead VSD Lag
Lead VFD Lag
*6
Friction Loss Calc
selection
Linear, Exponential
Linear
*7
Access Code
number
Off, 0 - 250
21
Serial Comms
selection
Output Cont Data, Modbus Protocol
Modbus Protocol
Modbus Address
number
1 - 31
1
Flow Sensing
selection Calculated, Scaled AnInp2, Digital Pulse
Calculated
Manual Run
selection
Input or P_But’n, Input Only
Input or P_But’n
*
These menus are related to other settings. They are not visible unless related settings are enabled
*1
Only shown if Operating Mode is set to Level.
*2
These menus show a value that is decoupled from the value that you are changing. Thus one press up
and one press down may not corresponded to +1 or -1 change in value.
*3
These settings are by default setup for a 4-20ma sensor with the range of 0-25bar (2500 kpa).
However it is still highly recommended that you calibrate the Speedman for your sensor.
*4
These menus are only visible when one of the Analogue inputs is configured as a flow meter.
*5
Menu hidden when Analogue output 2 is configured as VSD speed.
*6
Menu hidden when in level mode.
*7
The Access Code allows you to change the access code and also determine which features require
you to enter an access code.
*8
Menu hidden unless “JP Fallback” is set to “On” in the CONFIGURE Menu.
*9
Menu hidden unless “Analogue Input 2” is set to “Backup Pressure” in the CONFIGURE Menu.
*
Whether or not these options are shown depend on how many pumps are configured in the Configuration Menu.
Sub Menu
Units
Range
Defaults
PUMP DEFINITIONS
Pump 1
selection
Duty,Jockey
Duty
*
Pump 2
selection
Duty
Duty