Davey Speedman Dual Pump Variable Speed Pump Control System User Manual
Page 16

16
*
These menus are related to other settings. They are not visible unless related settings are enabled.
Sub Menu
Units
Range
Defaults
PIPE FILL
Pipe Fill Mode
selection
On, Off
Off
*
Jump Ramp Time
seconds
Off, 1 - 999
Off
*
Jump Final Speed
%
0-100%
50
*
Pipe Fill Time
seconds
5 - 999
100
*
Pipe Empty Pressure
Unitless
0 - 9999
200
*
Pipe Empty Time
seconds
0 - 999
200
Sub Menu
Units
Range
Defaults
INPUTS
Program Input 1
selection
VSD Fault
Program Input 2
selection
No Flow
Program Input 3
selection
Pump 1 Manual Run
Program Input 4
selection
Pump 1 Stop
Program Input 5
selection
Not selected
Program Input 6
selection
Not selected
Program Input 7
selection
Reset
Program Input 8
selection
Soft Pause
Any of the
following can be
selected on any
input and used
multiple times
Not selected,
Set Point 2 - 8,
Soft Pause,
Soft Pause JP
Run,
Emergency Stop,
Pump 1 - 6
Protection,
Pump 1 - 6 Stop,
Pump 1 - 6
Manual Run,
Fire Mode, Cycle
Pumps,
Shutdown Verify,
VSD Fault, Reset,
No Flow,
Aux Input 1 - 3,
Pump 1 - 6 No
Flow Protection,
Flow Pulse,
Low Level Pause
Analogue Input 1
selection
Disabled, Control
Pressure, Flow,
Set Point Input
Pressure
Analogue Input 2
selection
None, Control
Pressure, Flow,
Set Point Input,
Backup Pressure
None