PUMP PROTECTION

The Speedman has numerous safety features built into the system to protect the pumps from damage. Some
of these shut down all operations and some are designed to halt operations until the system can stabilise. The
user determines the selection of each of these.

Description

Screen Message

Action

High Pressure

Shutdown

HiPress Shutdown

Shutdown - Restart Automatically or Manually

Low Pressure

Shutdown

LoPress Shutdown

Shutdown - Manual restart

No Flow Shutdown

Low Flow Detected

No Flow Shutdown

On first detecting a “No Flow Input”

Shutdown - Manual Restart

Emergency Stop

Emergency Stop

Halts the system until contacts opened again

Individual Pump

Protection (Pause)

P X Protection

Pump 1-2 Halted until fault is removed

Individual Pump

Fault (Stop)

P X Fault

Pump 1-2 Shutdown, requires operator reset

High Pressure Shutdown

If the system pressure exceeds the High Pressure Shutdown setting for a period of time set by the High
Pressure Delay, the Speedman will shutdown the system until manually reset. The pressure reached will stay
on the display until the fault is reset.
There is the option to allow a number of automatic restarts after this shutdown.
There are 0-250 restarts possible and are set in the “High Pressure Restarts” screen within the TUNING menu.

Low Pressure Shutdown

If the system drops under the specified Low Pressure Shutdown setting for a period of time set by the Low
Pressure Delay the Speedman will shutdown the system until manually reset. Retries are not available for this
Fault.

Individual Pump Protection - P 1-2 Prot(Pause)

The Speedman has inputs for each pump to allow for individual pump protection. In the event of a pump going
into a fault condition the input for that pump should close. This will halt the pump after the time set by the Input
Delay Timer.
The pump will automatically restart when the Input contact is opened.
This protection is ideal for the following pump protection sensors:

Temperature probes

Thermal Overload

Thermistor relays

Individual No flow Pump Protection P 1-2 Fault(Stop)

Speedman has inputs for each pump to allow for individual No Flow pump protection. In the event of a pump
going into a fault condition the input for that pump should close. This will shut down the pump after the time set
by the No Flow Delay Timer.
The pump will NOT automatically restart when this event occurs.
This protection is ideal for the following pump protection sensors:

Temperature probes

Loss of prime flow switches

Thermal Overload

Thermistor

ALL FAULTS CAN BE REMOTELY RESET FROM THE “RESET INPUT”