Davey Speedman Dual Pump Variable Speed Pump Control System User Manual
Page 26
26
Pressure Trip 1 High
The High Trip point has a matching low Trip point. If a single trip
point is required, set the High and Low trip points to the same value. Note: The
settings of Trip high must be greater than or equal to Trip low. The system
does not allow settings to be selected outside this range.
The “Pressure Trip 1 Low” and “Pressure Trip 1 High” screens will only appear if an output is set to “Pressure
Trip 1” within the OUTPUTS menu.
Pressure Trip 2 Low
Operates as per Pressure Trip 1 Low.
Pressure Trip 2 High
Operates as per Pressure Trip 1 High.
The “Pressure Trip 2 Low” and “Pressure Trip 2 High” screens will only
appear if an output is set to “pressure trip 2” within the OUTPUTS menu.
Flow Trip Low
This setting is used to energise an output relay if the flow rate is below this
figure. The delay time for this setting is defined in the TIMING Menu under
Flow Trip Low Delay Time. See OUTPUTS for additional information.
Flow Trip High
Low Trip High can be set to deactivate an output relay
if the flow rate exceeds a nominated value. The delay time for this setting is defined
in the TIMING menu under “Flow Trip High Delay Time”.
See OUTPUTS for additional information.
The “Flow Trip Low” and “Flow Trip High” screens will only appear if an output is set to “flow trip” within the
OUTPUTS menu.
Press Trip 1 Hi
XXXX
Press Trip 2 Low
XXXX
Press Trip 2 Hi
XXXX
Flow Trip Low
XXXX /Sec
Flow Trip High
XXXX /Sec